Daikin GCU2040PXB1 [114/177] Copyright hpl january 2021 p4115s rev 02

Daikin GCU2040PXB1 [114/177] Copyright hpl january 2021 p4115s rev 02
58
ENG
pRack PR300T +0300018EN rel. 1.5 - 02.05.2017
Mask index Display description Description Def. U. of M.Values
Bab65 --- Common oil receiver pressure probe position (line 2) --- --- U1…U10 (****)
--- Common oil receiver pressure probe type (line 2) 4...20mA --- ----, 0-1V
0-10V
4...20mA
0-5V
--- (display only) Common oil receiver pressure value (line 2) --- …(**)
Max limit Maximum common oil receiver pressure value (line 2) 44.8 barg …(**)
Min limit Minimum common oil receiver pressure value (line 2) 0.0 barg …(**)
Calibrat. Common oil receiver pressure probe calibration (line 2) 0.0 barg …(**)
Bab75 --- Discharge pressure probe position (line 1) --- --- U1…U10 (****)
--- Discharge pressure probe type (line 1) 4...20mA --- ----, 0-1V
0-10V
4...20mA
0-5V
--- (display only) Discharge pressure value (line 1) --- …(**)
Max limit Maximum discharge pressure value (line 1) 44.8 barg …(**)
Min limit Minimum discharge pressure value (line 1) 0.0 barg …(**)
Calibrat. Discharge pressure probe calibration (line 1) 0.0 barg …(**)
…… ………
Bac02 Line relay DO Compressor 1 line relay DO position and status (On/O ) display (line 1) --- --- | 01…18 (****)
Part winding DO/Star relay
DO (*)
Compressor 1 part winding or star DO position and status (On/O ) display (line 1)
--- --- | 01…18 (****)
---/Delta relay DO (*) Compressor 1 delta DO position and status (On/O ) display (line 1) --- ---, 01…18 (****)
Logic Logic for compressor 1 power supply DO (line 1) NO --- NC | NO
Bac03 DO Compressor 1 unloader 1 DO position (line 1) --- ---, 01…18 (****)
Status (display only) Status for compressor 1 unloader 1 DO (line 1) --- --- Closed | Open
Logic Logic for compressor 1 unloader 1 DO (line 1) NO --- NC | NO
Function (display only) Compressor 1 unloader 1 function status (line 1) --- --- Not active | Active
…… ………
Bac71 DO Solenoid valve DO position for managing common oil di erential --- --- ---, 01…18 (****)
Status (display only) Solenoid valve DO status for managing common oil di erential --- --- Closed | Open
Logic Solenoid valve DO logic for managing common oil di erential NC --- NC | NO
Function Status of the solenoid valve for managing common oil di erential --- --- Not active | Active
Bacef DO Line relay DO position and On/O Status Parallel compressor consent ---, 01…18 (****)
Logic: Logic Parallel compressor consent DO: NA NC | NA
…… ………
Bad01 AO Compressor modulating device AO position (line 1) 0 --- ---, 01…06 (****)
Status (display only) Modulating device output value (line 1) 0 % 0.0…100.0
…… ………
Bb01 Suction L1 Suction line 1 in manual mode Disabled --- Disabled | abled
Suction L2 Suction line 2 in manual mode Disabled --- Disabled | abled
Condenser L1 Condenser line 1 in manual mode Disabled --- Disabled | abled
Condenser L2 Condenser line 2 in manual mode Disabled --- Disabled | abled
Timeout Manual mode duration after last key pressed 10 min 0…500
Bba02
Compressor 1
Force to
Manual stages request for compressor 1 (line 1)
OFF --- OFF | ON
2 STAGES (*)
3 STAGES (*)
4 STAGES (*)
…… ………
Bba16
Compressor 12
Force to
Manual stages request for compressor 12 (line 1)
OFF --- OFF | ON
2 STAGES (*)
3 STAGES (*)
4 STAGES (*)
Bba17 Oil Cool. pump 1
Force to
Manual operation status for oil cooling pump 1 (line 1)
OFF --- OFF | ON
Oil cool pump 2
Force to
Manual operation status for oil cooling pump 2 (line 1)
OFF --- OFF | ON
Bba18 Oil cool fan 1
Force to
Manual operation status for oil cooling fan 1 (line 1)
OFF --- OFF | ON
Bba20
Compressor 1
Force to
Manual stages request for compressor 1 (line 2)
OFF --- OFF | ON
2 STAGES (*)
3 STAGES (*)
4 STAGES (*)
…… ………
Bba34
Compressor 12
F
or
ce to
Manual stages request for compressor 12 (line 2)
OFF --- OFF | ON
2 STAGES (*)
3 STAGES (*)
4 STAGES (*)
Bba35 Oil Cool. pump 1
Force to
Manual operation status for oil cooling pump 1 (line 2)
OFF --- OFF | ON
Oil Cool. pump 2
Force to
Manual operation status for oil cooling pump 2 (line 2)
OFF --- OFF | ON
Bba37 Oil cool fan 1
Force to
Manual operation status for oil cooling fan (line 2)
OFF --- OFF | ON
Bba38 Fan 1
Force to
Manual operation status for fan 1 (line 1)
OFF --- OFF | ON
…… ………
Bba53 Fan 16
Force to
Manual operation status for fan 16 (line 1)
OFF --- OFF | ON
Bba54 Heat rec.pump
Force to
Manual operation status for heat recovery pump (line 1)
OFF --- OFF | ON
Bba55 ChillBooster
Force to
Manual operation status for ChillBooster (line 1)
OFF --- OFF | ON
Bba57 Fan 1
Force to
Manual operation status for fan 1 (line 2)
OFF --- OFF | ON
…… ………
Bba72 Fan 16
Force to
Manual operation status for fan 16 (line 2)
OFF --- OFF | ON
Bba73 Heat rec.pump
Force to
Manual operation status for heat recovery pump (line 2)
OFF --- OFF | ON
Bba74 ChillBooster
Force to
Manual operation status for ChillBooster (line 2)
OFF --- OFF | ON
Bbb05 Compressor 1
Force to
Manual request for continuous capacity for compressor 1 (line 1)
0.0 % 0.0…100.0
Page 114 of 177
Copyright HPL January 2021
P4115S Rev 02

Содержание