pRack PR300T +0300018EN rel. 1.5 - 02.05.2017
Menu access
The following are the steps for accessing the pendrive management
menu. Procedure:
1. Connect the pendrive to the master port.
USB key
BMS card
Fig. 10.k
2. Press Alarm and Enter together for 3 seconds to enter the option
menu. Select FLASH/USB memory and press Enter to con rm.
4:45&.*/'03."5*0/
-0(%"5"
05)&3*/'03."5*0/
'-"4)64#.&.03:
Fig. 10.l
3. Select USB pen drive and press Enter to con rm.
/"/%'-"4)'*-&4
64#1&/%3*7&
Fig. 10.m
Important: Wait a few seconds after the pendrive has been
plugged in for it to be recognised by the controller. If the message “No
USB disk or PC connected” is displayed momentarily with the request to
connect a pendrive key or computer USB cable, wait a few seconds until
the recognition message is shown (“USB disk found”) and the following
screen appears.
4. Select UPLOAD.
4ELECTFUNCTION
61-0"%PENP$0
%08/-0"%P$0PEN
Fig. 10.n
10.3.2 Upload
An application plus BIOS or bu er memory (parameters) can be uploaded
from the pendrive. The following modes are available: automatic, autorun
and manual. Automatic and autorun modes require using con guration les.
Con guration le structure
Con guration  les must start with the string “[FUNCTION]” followed by a
string that identi es the function, as shown in the table.
Function String
UPLOAD an application or a BIOS  le plus an
application
Upload application
UPLOAD non-volatile memory (.dev) Upload non volatile memory
UPLOAD the entire contents of the pRack Copy pRack upload
After the description of the desired function, various options are available:
1. To copy the complete contents of the directory, simply write the
name of the directory (e.g. the entire contents of the CHILLER
directory):
[FUNCTION]
Upload non volatile memory
[DIR]
CHILLER
2. To copy just 1  le in a directory, enter the  les name (e.g. the
CHILLER.DEV  le in the CHILLER directory).
[FUNCTION]
Upload non volatile memory
[DIR]
CHILLER
CHILLER.DEV
To show a string on the display describing the operation being
performed, add the “[NAM]” instruction, followed by the string to display.
The following  le will display the string:
“UPL CHILLER.DEV
[FUNCTION]
Upload non volatile memory
[DIR]
CHILLER
[NAM]
UPL CHILLER.DEV
CHILLER.DEV
3. To select only some of the  les in the same directory, list them after
a label. The following labels are allowed and must be entered in the
order shown in the table:
UPLOAD  le labels
No. Label File type No. Label File type
1 [BIO] (*) le.bin 6 [PVT] le.pvt
2 [IUP] le.iup 7 [LCT] le.lct
3 [BIN] le.bin, blb 8 [OED] le.oed
4 [DEV] le.dev 9 [SGN] le.sgn
5 [GRP]  le.grp
(*) BIO = BIOS  le
Notes:
to get the.bin file from the BIOS in the format available on http://ksa.
carel.com (.os file), unzip the.os file;
the [IUP] label can be followed by one or more .iup” files.
Important:
the order in which the  le names are entered is fundamental and must
not be changed;
do not enter empty lines or spaces in the  le (e.g. at the end of a line);
each  le after the last line of code must contain a carriage return
character (CR ), as shown in the following example.