Haier HCFU-18CF03 Сервис мануал онлайн [61/91] 612387

Haier HCFU-28CF03 Сервис мануал онлайн [61/91] 612389
(2) Auto Selection of Wind Speed
In the following, Tr means room temperature while Ts means setting temperature.
a. During cooling program conversion of wind speed from the low to high won’t work until
the present speed has continued for 3 minutes while conversion from the high to low needs
no time delay. The chart below is the sketch map of conversion:
Ts 2
Ts 1
Medium speed
Medium speed
Temperature
falling
Temperature
rising
Low speed
High speed
Low peed
High speed
Ts
3
Ts
b. During heating program applicable for cooling-heating type , conversion of wind speed
from the low to high won’t work until the present speed has continued for 3 minutes while
conversion from the high to low needs no time delay. The hart below is the sketch map of
conversion:
Low speed
Ts 1
Ts 2
Medium speed
Medium speed
Temperature
rising
High speed
High speed
Temperature
falling
Ts
Low speed
Ts
3
(3) Dehumidifying program
In the following, Tr means room temperature while Ts means setting temperature.
a. After the system entering dehumidifying program, the compressor, outdoor and indoor
blowing fans run according to the following rules:
(1) Tr > Ts + 2
, the compressor and outdoor blowing fan run continuously while indoor
Commercial Air Conditioner Model: HCFU-18/28CF03
HCFU-18/28HF03
61