Haier HCFU-18CF03 [83/91] Commercial air conditioner

Haier HCFU-18HF03 [83/91] Commercial air conditioner
0010451167 PCB information – function selection
˄
ON is 1, OFF is 0
˅
The standard condition for PCB in factory
SW1˖4 bits are OFF
SW2˖4 bits are OFF
SW3˖4 bits are ON
SW4˖2 bits are ON
SW5˖4 bits are ON
SW1-SW2: used for indoor unit to set unit address from 1 to 16’
SW3-SW5: used for indoor unit to select different functions.(every dip switches are corresponding to
J1-J10.
SW2-4üülogistic relationship of control function˄door card control and remote/ wired control˅0
means logistic relationship is “and”, 1 means the later coming is preferential.
J1ˈSW3-1üüfunction selection-control type: 1 means remote control, 0 means wired control.
J2ˈSW3-2üüfunction selection-temperature compensation in heating mode: 1means “yes”, 0means
“no”.
J3ˈSW3-3üüfunction selection-outdoor communication: 1means “yes”, 0means “no”. This PCB
must be 1.
J4ˈSW3-4üüfunction selection-heat pump unit: 1means “heat pump”, 0means “cooling only”.
1/60üütest in short circuit, but in operation short circuit mustn’t be permitted.
CHECKüüshort spring switch control, it also can be used as switch of convertible type except for
testing.
J5ˈSW4-1üüfunction selection-outdoor pressure switch control function(if outdoor is without PCB):
1means the pressure switch is invalid, 0 means the pressure switch is valid.
J6ˈSW4-2üüfunction selection –outdoor defrosting temp. sensor control function(when outdoor is
without PCB): 1means outdoor defrost temp. sensor is invalid; 0 means outdoor defrost temp. sensor is
valid.
J7ˈSW5-1üüfunction selection –swing mode: 1 means common˄simultaneous motor˅, 0 means
special (swing motor).
J8ˈSW5-2üüfunction selection – system combination: 1means fixed frequency single unit, 0 means
fixed frequency multi split.
J9ˈSW5-3üüfunction selection –group control: 1 stands for the master unit (its address in wired
controller is 0), 0 stands for the slave units (the address should be set by the dip switch, their addresses
only can be in the range: 1~15)
J10ˈSW5-4üüfunction selection –preset: 1 no meaning, 0 no meaning
Commercial Air Conditioner Model: HCFU-18/28CF03
HCFU-18/28HF03
83