Haier HSU-09H03/R(DB) Сервис мануал онлайн [19/131] 613257

Haier HSU-12H03/R(DB) Сервис мануал онлайн [19/131] 613258
,QGRRUEORZHUIDQFRQWURO

When the wind volume is manually medium, the running speed is
(strong+weak)/2.
When it is automatically medium, the running speed is (strong automatic+
weak automatic)/2(not counted if it is not up to 10rpm)
Warm boot When the heat running starts or the frost removing ends and the compressor
starts again, in order to avoid cold wind, warm boot wind volume control
should be done.
Heat exchange temperature

To control the indoor blower fan as shown in the table above according to the
heat exchange temperature
When the heat exchange temperature rises to the level between THHOT1 and
HHOT2 and even after 4 minutes it cannot reach the level between THHOT2
and THHOT3, enter into the next level without referring to the heat exchange
temperature.
the blower fan stops when the heat exchange temperature is below 25ć
the blower fan is working slightly weak when he heat exchange
temperature is above 25 ć and below 35ć
the blower fan is working weak if the he heat exchange temperature remains
35ć for less than 4 minutes.
The blower fan works as set if the he heat exchange temperature remains 35
ć for more than 4 minutes
the blower fan works as set if the he heat exchange temperature remains
above 37ć
Note: the numerical value above may not the same as the numerical value in
indoor MCU.
the compressor 20 seconds after the compressor stops, the wind volume is weak(switching
+6809,12H03/R(DB)  Functions and control
Demastic Air Conditioners
16