Step 6 Charging ENGLISH Charge the system using the weight method The unit comes with enough charge for 25 feet per circuit For example the 2 port unit will come with 50 feet of charge the3 port unit will come with 75 feet of charge and the 4 port unit will come with 100 feet of charge If the system must have additional charge added add 2 ounces of charge for every additional foot of refrigerant line that is above factory charge If the total of distance of the installed line sets is below factory charge the factory charge is sufficient Simply release the charge by opening the system service valves Step 7 System Test Check Items for Test Run Put check mark V inboxes No gas leak from linesets Are the linesets insulated properly Are the connecting wirings of indoorand outdoorfirmly inserted to the terminal block Isthe wiring of indoor and outdoor firmly fixed Is condensate draining correctly Is the ground wire secure Is the indoor unit secured Is power source voltage correct according to local code Is there any noise Is the lamp normally lighting Are cooling and heating performing normally Is the operation of room temperature sensor normal Step 8 Explaining Operation to the End User Using the OPERATING INSTRUCTIONS explain to the user how to use the air conditioner the remote controller removing the air filters placing or removing the remote controller from the remote controller holder cleaning methods precautions for operation etc Recommend that the user read the OPERATING INSTRUCTIONS carefully PAGE 12 INSTALLATION