02_NVspec_ver202e_pdf.xls 4_Network Variables
16
n
Alarm state
network output SNVT_switch nvoAlarm_n;
This output network variable indicates the abnormality of the indoor unit.
If the outdoor unit is in alarm state, the indoor unit also stops urgently.
Therefore all indoor units in a same refrigerant system will transmit alarm state
when the outdoor unit is under alarm state.
However the indoor unit under stopping is excluded.
Valid Range
value field: not used = 0 constantly
state field : 0 = Normal
state field : 1 = Alarm
*The value is 0 while LM-AP is initialized.
When Transmitted
This variable is transmitted promptly as the state changes.
Update Rate
Update RateUpdate Rate
Update Rate
The maximum update rate is not available.
Default Service Type
Acknowledged
NOTE: The release of the indoor unit nvoAlarm_ (Alarm State) results in the "Off"
command of the nviOnOff_ (Request On/Off).
For the nvoAlarm_n (Alarm State) when the indoor unit is under stopping, transmit "Off" .
after transmitting "On"
WLN01-1023(Ver2.02) - 15 -