Mitsubishi Electric LMAP-02E [19/25] Request all off
![Mitsubishi Electric LMAP-02E [19/25] Request all off](/views2/1081505/page19/bg13.png)
02_NVspec_ver202e_pdf.xls 4_Network Variables
11
Request All Off
network input SNVT_switch nviAllOff;
This input network variable is used for the emergency Off of the indoor unit and all ventilation.
Valid Range
value field : not used
state field : 0 = Emergency Off of indoor unit and ventilator
: Else = not used
Default Value
The default value is determined by the state of the air conditioner (indoor unit).
This variable becomes value = 0 until the value is updated after the power supply of LM-AP.
WLN01-1023(Ver2.02) - 19 -
Содержание
- Air conditioner interface 1
- Mitsubishi electric 1
- Model lmap02 e pac yv02lmap 1
- Network variables specification 1
- Programid 9 00071 0076 0002 02 xif lm02_02 xif 1
- 1 multiple split type air conditioners city multi 2 split type air conditioners mr slim 2
- 1 object model 2
- 2 explanation of function setting 2
- Heat recovery ventilators lossnay 2
- Lmap can be connected with the following models made by mitsubishi electric corporation 2
- Specification 2
- The function set switch is necessary for this product because of connected model and the control function from 2
- 1 overview 3
- Indoor0 3
- Indoor1 3
- Indoor50 3
- Node object 3
- 2222 object details 3
- Snvt table 3 snvt table 3 snvt table 3 snvt table 8
- Default service type 9
- Default value 9
- Network variables 9
- On off run state 9
- Request on off 9
- Update rate update rate update rate update rate 9
- Valid range 9
- When transmitted 9
- Default service type 10
- Default value 10
- Mode state 10
- Request mode 10
- Update rate update rate update rate update rate 10
- Valid range 10
- When transmitted 10
- Default service type 11
- Default value 11
- Lossnay mode state 11
- Request lossnay mode 11
- Update rate update rate update rate update rate 11
- Valid range 11
- When transmitted 11
- Default service type 12
- Default value 12
- Setpoint from network both cool and heat 12
- Setpoint state both cool and heat 12
- Update rate update rate update rate update rate 12
- Valid range 12
- When transmitted 12
- Default service type 13
- Default value 13
- Fan speed state 13
- Request fan speed 13
- Update rate update rate update rate update rate 13
- Valid range 13
- When transmitted 13
- Default service type 14
- Indoor temperature state 14
- Thermo on off state 14
- Update rate update rate update rate update rate 14
- Valid range 14
- When transmitted 14
- Alarm state 15
- Default service type 15
- Update rate update rate update rate update rate 15
- Valid range 15
- When transmitted 15
- Default service type 16
- Default value 16
- Local prohibit on off state 16
- Request local prohibit on off 16
- Update rate update rate update rate update rate 16
- Valid range 16
- When transmitted 16
- Default service type 17
- Default value 17
- Local prohibit mode state 17
- Request local prohibit mode 17
- Update rate update rate update rate update rate 17
- Valid range 17
- When transmitted 17
- Default service type 18
- Default value 18
- Local prohibit setpoint state 18
- Request local prohibit setpoint 18
- Update rate update rate update rate update rate 18
- Valid range 18
- When transmitted 18
- Default value 19
- Request all off 19
- Valid range 19
- Configuration properties 5 configuration properties 5 configuration properties 5 configuration properties 20
- Default value 20
- Send heartbeat_1 20
- Send heartbeat_2 20
- Valid range 20
- Default value 21
- Initialize start time 21
- Minimum send time 21
- Valid range 21
- Default value 22
- Initialize send time_1 22
- Initialize send time_2 22
- Valid range 22
- Default value 23
- Send heartbeat start time 23
- Send start time 23
- Valid range 23
- Object request 24
- Object status 24
- Centralized 25
- Communication timing when power supply of lm ap is turned on 25
- Controller 25
- Indoor unit 25
- Power supply power supply power supply power supply power supply tttt initialized processing initialized processing initialized processing initialized processing usually processing usually processing usually processing usually processing 25
Похожие устройства
- Hitachi CJ120VA Инструкция по эксплуатации
- JVC GZ-E209BEU Инструкция по эксплуатации
- Mitsubishi Electric PAR-FL32MA Инструкция по эксплуатации
- Hitachi CR13V2 Инструкция по эксплуатации
- Prology iMAP-527MG Инструкция по эксплуатации
- Mitsubishi Electric PAR-FA32MA Инструкция по эксплуатации
- Hitachi CJ65V3 Инструкция по эксплуатации
- Prestigio GeoVision 5800BTHDDVR Инструкция по эксплуатации
- Mitsubishi Electric PAR-30MAA Инструкция по эксплуатации
- Hitachi CR13VBY Инструкция по эксплуатации
- Prology iMAP-560TR Инструкция по эксплуатации
- Mitsubishi Electric PAR-21MAA Инструкция по эксплуатации
- Hitachi F30A Инструкция по эксплуатации
- Prestigio GeoVision 4130 Инструкция по эксплуатации
- Mitsubishi Electric PAC-YT40ANRA Инструкция по эксплуатации
- Hitachi P20SA2 Инструкция по эксплуатации
- Hyundai H-DVR11HD Инструкция по эксплуатации
- Mitsubishi Electric PAC-YT32PTA Инструкция по эксплуатации
- Hyundai H-DVR08HD Инструкция по эксплуатации
- Hitachi P20SB Инструкция по эксплуатации