02_NVspec_ver202e_pdf.xls 5_Configuration
(3)
Minimum Send Time
network in
p
ut confi
g
SNVT_time_sec nciMinOutTm
;
This configuration property defines the minimum send time between the output network variables.
The objective network variables are given below.
・nvoOnOff_n(On/Off Run State )
・nvoMode_n(Mode State)
・nvoLCMode_n(LOSSNAY Mode State)
・nvoSetPoint_n(Setpoint State)
・nvoFanSpeed_n(Fan Speed State)
・nvoThermo_n(Thermostat On/Off State )
・nvoSpaceTemp_n(Indoor Temperature State )
・nvoAlarm_n(Alarm State)
・nvoProOnOff_n(Local Prohibit On/Off State)
・nvoProMode_n(Local Prohibit Mode State)
・nvoProSetP_n(Local Prohibit SetPoint State )
Valid Range
The valid range covers from 0,1.0 to 600.0 seconds (per 1 second).
The setting to 0.0 or 6553.5 seconds makes the minimum send time setting invalid.
The setting to 0.1 ~ 0.9 seconds results in 1.0 second.
The setting to 600.1 ~ 6553.4 seconds results in 600.0 seconds.
Default Value
6553.5 seconds (Setting invalid)
(4)
Initialize Start Time
network in
p
ut confi
g
SNVT_time_sec nciInitStartTm
This configuration property defines the starting time of the output network variables at the initial output.
The objective network variables are given below.
・nvoOnOff_n(On/Off Run State )
・nvoMode_n(Mode State)
・nvoLCMode_n(LOSSNAY Mode State)
・nvoSetPoint_n(Setpoint State)
・nvoFanSpeed_n(Fan Speed State)
Valid Range
The valid range covers from 0.0,900.0 to 3600.0 seconds (per 60 seconds).
The setting to 0.0 or 6553.5 seconds makes the initial output time setting invalid.
The setting to 0.1 ~ 899.9 seconds results in 900.0 seconds.
The setting to 3600.1 ~ 6553.4 seconds results in 3600.0 seconds.
Default Value
6553.5 seconds (Setting invalid)
WLN01-1023(Ver2.02) - 21 -
Содержание
- Air conditioner interface 1
- Mitsubishi electric 1
- Model lmap02 e pac yv02lmap 1
- Network variables specification 1
- Programid 9 00071 0076 0002 02 xif lm02_02 xif 1
- 1 multiple split type air conditioners city multi 2 split type air conditioners mr slim 2
- 1 object model 2
- 2 explanation of function setting 2
- Heat recovery ventilators lossnay 2
- Lmap can be connected with the following models made by mitsubishi electric corporation 2
- Specification 2
- The function set switch is necessary for this product because of connected model and the control function from 2
- 1 overview 3
- Indoor0 3
- Indoor1 3
- Indoor50 3
- Node object 3
- 2222 object details 3
- Snvt table 3 snvt table 3 snvt table 3 snvt table 8
- Default service type 9
- Default value 9
- Network variables 9
- On off run state 9
- Request on off 9
- Update rate update rate update rate update rate 9
- Valid range 9
- When transmitted 9
- Default service type 10
- Default value 10
- Mode state 10
- Request mode 10
- Update rate update rate update rate update rate 10
- Valid range 10
- When transmitted 10
- Default service type 11
- Default value 11
- Lossnay mode state 11
- Request lossnay mode 11
- Update rate update rate update rate update rate 11
- Valid range 11
- When transmitted 11
- Default service type 12
- Default value 12
- Setpoint from network both cool and heat 12
- Setpoint state both cool and heat 12
- Update rate update rate update rate update rate 12
- Valid range 12
- When transmitted 12
- Default service type 13
- Default value 13
- Fan speed state 13
- Request fan speed 13
- Update rate update rate update rate update rate 13
- Valid range 13
- When transmitted 13
- Default service type 14
- Indoor temperature state 14
- Thermo on off state 14
- Update rate update rate update rate update rate 14
- Valid range 14
- When transmitted 14
- Alarm state 15
- Default service type 15
- Update rate update rate update rate update rate 15
- Valid range 15
- When transmitted 15
- Default service type 16
- Default value 16
- Local prohibit on off state 16
- Request local prohibit on off 16
- Update rate update rate update rate update rate 16
- Valid range 16
- When transmitted 16
- Default service type 17
- Default value 17
- Local prohibit mode state 17
- Request local prohibit mode 17
- Update rate update rate update rate update rate 17
- Valid range 17
- When transmitted 17
- Default service type 18
- Default value 18
- Local prohibit setpoint state 18
- Request local prohibit setpoint 18
- Update rate update rate update rate update rate 18
- Valid range 18
- When transmitted 18
- Default value 19
- Request all off 19
- Valid range 19
- Configuration properties 5 configuration properties 5 configuration properties 5 configuration properties 20
- Default value 20
- Send heartbeat_1 20
- Send heartbeat_2 20
- Valid range 20
- Default value 21
- Initialize start time 21
- Minimum send time 21
- Valid range 21
- Default value 22
- Initialize send time_1 22
- Initialize send time_2 22
- Valid range 22
- Default value 23
- Send heartbeat start time 23
- Send start time 23
- Valid range 23
- Object request 24
- Object status 24
- Centralized 25
- Communication timing when power supply of lm ap is turned on 25
- Controller 25
- Indoor unit 25
- Power supply power supply power supply power supply power supply tttt initialized processing initialized processing initialized processing initialized processing usually processing usually processing usually processing usually processing 25
Похожие устройства
- Hitachi CJ120VA Инструкция по эксплуатации
- JVC GZ-E209BEU Инструкция по эксплуатации
- Mitsubishi Electric PAR-FL32MA Инструкция по эксплуатации
- Hitachi CR13V2 Инструкция по эксплуатации
- Prology iMAP-527MG Инструкция по эксплуатации
- Mitsubishi Electric PAR-FA32MA Инструкция по эксплуатации
- Hitachi CJ65V3 Инструкция по эксплуатации
- Prestigio GeoVision 5800BTHDDVR Инструкция по эксплуатации
- Mitsubishi Electric PAR-30MAA Инструкция по эксплуатации
- Hitachi CR13VBY Инструкция по эксплуатации
- Prology iMAP-560TR Инструкция по эксплуатации
- Mitsubishi Electric PAR-21MAA Инструкция по эксплуатации
- Hitachi F30A Инструкция по эксплуатации
- Prestigio GeoVision 4130 Инструкция по эксплуатации
- Mitsubishi Electric PAC-YT40ANRA Инструкция по эксплуатации
- Hitachi P20SA2 Инструкция по эксплуатации
- Hyundai H-DVR11HD Инструкция по эксплуатации
- Mitsubishi Electric PAC-YT32PTA Инструкция по эксплуатации
- Hyundai H-DVR08HD Инструкция по эксплуатации
- Hitachi P20SB Инструкция по эксплуатации