02_NVspec_ver202e_pdf.xls 5_Configuration
(7)
Send Heartbeat Start Time
network in
p
ut confi
g
SNVT_time_sec nciStartHrtBt
This configuration property defines the start time of automatic updating at the powering of the LM-AP.
The objective network configurations are given below.
 ・nciSndHrtBt_1(Send Heartbeat_1)
 ・nciSndHrtBt_2Send Heartrbeat_2
Valid Range
The valid range covers from 0.0,1200.0 to 6540.0 seconds (per 60 seconds).
The setting to 0.0 or 6553.5 seconds results in 1800.0 seconds.
The setting to 0.1 1199.9 seconds results in 1200.0 seconds.
The setting to 6540.1 6553.4 seconds results in 6540.0 seconds.
Default Value
6553.5 seconds (judged as 1800 seconds)
(8)
Send Start Time
network in
p
ut confi
g
SNVT_time_sec nciStartOutTm
This configuration property defines the start time of the output network variable change at powering of
LM-AP.
The objective network variables are given below.
 ・nvoOnOff_nOn/Off Run State
 ・nvoMode_nMode State
 ・nvoLCMode_nLOSSNAY Mode State
 ・nvoSetPoint_nSetpoint State
 ・nvoFanSpeed_nFan Speed State
 ・nvoThermo_nThermostat On/Off State
 ・nvoSpaceTemp_nIndoor Temperature State
 ・nvoAlarm_nAlarm State
 ・nvoProOnOff_nLocal Prohibit OnOff State
 ・nvoProMode_nLocal Prohibit Mode State
 ・nvoProSetP_nLocal Prohibit SetPoint State
Valid Range
The valid range covers from 0.0,1200.0 to 6540.0 seconds (per 60 seconds).
The setting to 0.0 or 6553.5 seconds results in 1800.0 seconds.
The setting to 0.1 1199.9 seconds results in 1200.0 seconds.
The setting to 6540.1 6553.4 seconds results in 6540.0 seconds.
Default Value
6553.5 seconds (judged as 1800 seconds)
WLN01-1023(Ver2.02) - 23 -