Mitsubishi Electric LMAP-02E [2/25] Specification

Mitsubishi Electric LMAP-02E [2/25] Specification
02_NVspec_ver202e_pdf.xls 1_Object Model
1.Specification
1-1.Object Model
LMAP can be connected with the following models made by MITSUBISHI ELECTRIC CORPORATION.
<Model name>
1.
Multiple split type air conditioners CITY MULTI
2.
Split-type air conditioners Mr.SLIM
NOTE:Mr.SLIM is necessary for A-M Converter(PAC-SF48MA-E)
3.
Heat recovery ventilators LOSSNAY
NOTE:LOSSNAY is necessary for LOSSNAY Adapter(PZ-53ADF-E/PZ-52SF-E)
1-2.Explanation of Function Setting
The function set switch is necessary for this product because of connected model and the control function from L
ON
W
ORKS
.
SW NO.
SW NO.SW NO.
SW NO. switch name
switch nameswitch name
switch name Function
FunctionFunction
Function Note
NoteNote
Note
Factory
FactoryFactory
Factory
setting
settingsetting
setting
Set timing
Set timingSet timing
Set timing
SW1-1
SW1-1SW1-1
SW1-1 Function switch of local prohibit ON
ONON
ON local prohibit effective
Operation local prohibit nv input from
L
ON
W
ORKS
becomes Effective when switch ON.
OFF
Before turning on
the power supply
OFF local prohibit invalidity
Operation local prohibit nv input from
L
ON
W
ORKS
becomes invalid when switch OFF.
SW1-2
SW1-2SW1-2
SW1-2 Used together with MELANS switch ON
ONON
ON
used together
with MELNAS
OFF
Before turning on
the power supply
OFF
not used together
with MELNAS
SW1-3
SW1-3SW1-3
SW1-3
Indoor temperature state
interval switch
ON
ONON
ON
Transmission interval
(1minutes or more)
*The number of indoor unit should be
connected 30 or less
OFF
Before turning on
the power supply
OFF
Transmission interval
(10 minutes or more)
SW1-5
SW1-5SW1-5
SW1-5 Function switch of LOSSNAY ON
ONON
ON
LOSSNAY is operation
from LONWORKS.
Please turn on the switch when LOSSNAY
is operation from L
ON
W
ORKS
.
OFF
Before turning on
the power supply
OFF
LOSSNAY interlocks
with the indoor unit
Please turn off the switch when LOSSNAY
interlocks with the indoor units.
SW1-6
SW1-6SW1-6
SW1-6 Function switch of Mr.SLIM ON
ONON
ON
Mr.SLIM is operation
from LONWORKS.
Please turn on the switch when Mr.SLIM
is operation from L
ON
W
ORKS
OFF
Before turning on
the power supply
*Function effective at SW1-2 OFF OFF
Mr.SLIM is not operation
from LONWORKS.
SW1-9
SW1-9SW1-9
SW1-9 Indoor units test run switch ON
ONON
ON
ON(test run) is transmitted
to the indoor units
OFF Always
OFF
OFF is transmitted
to the indoor units
SW3-2
SW3-2SW3-2
SW3-2
Initialization switch of
the air conditioners units
ON
ONON
ON
Connected cancellation
command is transmitted to
the indoor units
OFF Always
OFF None
WLN01-1023(Ver2.02) - 2 -