VTS VENTUS PRO PVS PO 30 AC [15/25] Low outdoor air temperature and low outdoor absolute humidity

VTS VENTUS PRO PVS HY 60 [15/25] Low outdoor air temperature and low outdoor absolute humidity
VENTUS PRO - PVS PO – POOL DEHUMIDIFICATION UNIT VENTUS PRO - PVS PO – POOL DEHUMIDIFICATION UNIT
3130
1
2
3
1- LOW OUTDOOR AIR TEMPERATURE AND LOW OUTDOOR ABSOLUTE HUMIDITY
» Outdoor absolute humidity value is lower than 13,3 gr/kg.
» Outdoor dry bulb temperature is lower than 30°C.
» 1
st
operation mode is active.
» Bypass damper is active
» Compressors are off.
» Dehumidication process with fresh air mixure.
» Heating process with heat-pipe, if needed hot water heater gets activated as well.
EXHAUST FRESH AIR
SUPPLYRETURN
2- LOW OUTDOOR AIR TEMPERATURE AND HIGH OUTDOOR ABSOLUTE HUMIDITY
» Outdoor absolute humidity value is higher than 13,3 gr/kg.
» Outdoor dry bulb temperature is lower than 30°C.
» 2
nd
operation mode is active.
» Proportional mixing damper is active.
» Compressors are on.
» Dehumidication process with cooling and condensation of fresh air mixure.
EXHAUST FRESH AIR
SUPPLYRETURN