S+S Regeltechnik AERASGARD RFTM-LQ-CO2-W [11/32] Rco2 w rlq co2 w rftm lq co2 w rtm co2 sd

S+S Regeltechnik AERASGARD RFTM-LQ-CO2-W [11/32] Rco2 w rlq co2 w rftm lq co2 w rtm co2 sd
11
G
AERASGARD
®
RCO2 - W RLQ - CO2 - W RFTM - LQ - CO2 - W RTM - CO2 - SD
Rev. 2021 - V31
TECHNICAL DATA
(continued)
Ambient temperature: 0...+ 50 °C
Permitted humidity: 0...95 % r. H. (non-precipitating air)
Warm up time: approx. 1 hour
Response time: < 2 minutes
Electrical connection: 0.14 - 1.5 mm
2
, via screw terminals
Housing: plastic, material ABS, colour pure white (similar to RAL 9010),
stainless steel
V2A
(1.4301) housing optional
Dimensions: 98 x 98 x 33 mm (Baldur 2)
Installation: wall mounting or on in-wall flush box, Ø 55 mm, base with 4 holes, for attachment
to vertically or horizontally installed in-wall flush boxes for rear cable entry,
with predetermined breaking point for cable entry from top ⁄ bottom in case of plain on-wall installation
Protection class: III (according to EN 60 730)
Protection type:
IP 30
(according to EN 60 529)
Standards: CE conformity, electromagnetic compatibility according to EN 61 326,
EMC Directive 2014 ⁄ 30 ⁄ EU, Low Voltage Directive 2014 ⁄ 35 ⁄ EU
Optional:
display with illumination,
two line, cutout approx. 36 x 15 mm (W x H),
for displaying actual humidity, actual temperature, air quality and the actual CO2 content
AERASGARD
®
RTM - CO2 - SD
Room temperature and CO2 sensor, Standard
AERASGARD
®
RCO2 - W
Room CO2 sensor, Premium
AERASGARD
®
RLQ - CO2 - W
Room air quality (VOC) and CO2 sensor, Premium
AERASGARD
®
RFTM - CO2 - W
Multifunctional room sensor
for humidity, temperature and CO2 content, Deluxe
AERASGARD
®
RFTM - LQ - CO2 - W
Multifunctional room sensor
for humidity, temperature, CO2 content and air quality (VOC), Deluxe
Type ⁄ WG02 Measuring Range
Humidity Temperature CO
2
Equipment
VOC Display
Item No.
(Baldur 2)
RTM - CO2 - SD
(fixed)
RTM-CO2-SD-U 0...+50 °C 0...2000 ppm
1501-61B2-1001-200
RCO2 - W
(switchable)
RCO2-W 0...2000 ⁄ 5000 ppm W 1501-61A0-7301-200
RCO2-W
LCD
0...2000 ⁄ 5000 ppm W 1501-61B0-7321-200
RLQ - CO2 - W
(switchable)
RLQ-CO2-W 0...2000 ⁄ 5000 ppm 0...100 % W 1501-61B1-7301-500
RLQ-CO2-W
LCD
0...2000 ⁄ 5000 ppm 0...100 % W 1501-61B1-7321-500
RFTM - CO2 - W
(switchable)
RFTM-CO2-W 0...100 % r.H. 0...+50 °C 0...2000 ⁄ 5000 ppm W 1501-61B6-7301-200
RFTM-CO2-W
LCD
0...100 % r.H. 0...+50 °C 0...2000 ⁄ 5000 ppm W 1501-61B6-7321-200
RFTM - LQ - CO2 - W
(switchable)
RFTM-LQ-CO2-W 0...100 % r.H. 0...+50 °C 0...2000 ⁄ 5000 ppm 0...100 % W 1501-61B8-7301-500
RFTM-LQ-CO2-W
LCD
0...100 % r.H. 0...+50 °C 0...2000 ⁄ 5000 ppm 0...100 % W 1501-61B8-7321-500
Outputs:
0 -10 V or 4...20 mA
(selectable via DIP switches, selected variant applies for all outputs) –
Standard room sensor
RTM - CO2 - SD
with fixed output 0 -10 V!
Equipment:
W = changeover contact
Standard room sensor
RTM - CO2 - SD
without changeover contact !
Note:
This unit
must not
be used as safety-relevant device!

Содержание

Скачать