S+S Regeltechnik AERASGARD RFTM-LQ-CO2-W [19/32] Rco2 w rlq co2 w rftm lq co2 w rtm co2 sd

S+S Regeltechnik AERASGARD RFTM-CO2/RFTM-LQ-CO2 [19/32] Rco2 w rlq co2 w rftm lq co2 w rtm co2 sd
19
4
5
6
1 2 3
SET REL.
OFFSET
ZERO
CO
²
CO
²
VOC VOC
r.H.°C
121113
123 456 789
ON
DIP
ON ON
VOC CO
²
Mode
NC = Normally Closed
COM = Common
NO = Normally Open
Plug for
display
humidity in % r.H.
air quality (VOC)
Outputs
temperature in °C
–UB GND
+UB 24V AC/DC
Output CO
²
in ppm
VOC
sensor
Reset
button
NC
COM
NO
relay
switch
point
4
5
6
1 2 3
ZERO
CO
²
free
free
Outputs
temperature in °C
–UB GND
+UB 24V AC/DC
Output CO
²
in ppm
Reset
button
F
AERASGARD
®
RCO2 - W RLQ - CO2 - W RFTM - LQ - CO2 - W RTM - CO2 - SD
Rev. 2021 - V31
Schéma de raccordement
RFTM - LQ
- CO2 - W
Schéma de raccordement
RTM - CO2 - SD
Interrupteur DIP (Baldur 2)
RFTM - LQ
- CO2 - W
Sensibilité COV DIP 1 DIP 2
LOW OFF OFF
MEDIUM (default)
O N
OFF
HIGH OFF
O N
IAQ
(Indoor Air Quality)
O N O N
Teneur en CO2 DIP 4
0...2000 ppm (default) OFF
0...5000 ppm
O N
Type d’étalonnage CO2 DIP 6
désactivé OFF
activé (default)
O N
Affectation relais DIP 7 DIP 8
CO2 (default) : 600...1900 ppm / 900...4700 ppm OFF OFF
COV : 10...95 %
O N
OFF
Temrature : +5...+48 °C OFF
O N
Humidité : 10...95% r.H.
O N O N
Sortie DIP 9
Tension 0 -10 V (default) OFF
Courant 4...20 mA
O N
Remarque :
DIP 3
e
DIP 5
ne sont pas affecs !
Niveau IAQ
(Indoor Air Quality)
COV
1 Très bonne 0
...
19
%
aucune mesure nécessaire
2 bonne 20
...
39
%
aération recommandée prochainement
3 moyenne 40
...
59
%
aération recommandée
4 mauvaise 60
...
79
%
aération prolongée nécessaire
5 Très mauvaise 80
...
100
%
aération intensive indispensable
Tableau conforme aux directives COVT du Ministère fédéral de
l’Environnement pour l’évaluation du niveau de contamination de
l’air intérieur
(Journal du Ministère fédéral de la santé - Recherche en santé -
Protection de la santé 2007, 50: 990–1005)

Содержание

Скачать