Moxa OnCell G3150-HSPA [28/172] Serial console

Moxa OnCell G3110-HSPA-T [28/172] Serial console
OnCell G3100 Series Initial IP Address Configuration
3-7
Serial Console
The OnCell G3100 supports configuration through the serial console, which is the same as the Telnet console
but accessed through the RS-232 console port rather than over the network. Once you have entered the serial
console, the configuration options and instructions are the same as if you were using the Telnet console.
The following instructions and screenshots show how to enter the serial console using PComm Terminal
Emulator, which is available free of charge as part of the PComm Lite suite. You may use a different terminal
emulator utility, although your actual screens and procedures may vary slightly from the following instructions.
1. Turn off the power to the OnCell G3100. Use a serial cable to connect the OnCell G3100’s serial console port
to your computer’s RS-232 serial port.
2. From the Windows desktop select Start
All Programs
PComm Lite
Terminal Emulator.
3. The PComm Terminal Emulator window should appear. From the Port Manager menu, select Open, or
simply click the Open icon as shown below:
4. The Property window opens automatically. Select the Communication Parameter tab, and then select
the appropriate COM port for the connection (COM4 in this example). Configure the parameters for 115200,
8, N, 1 (115200 for Baudrate, 8 for Data Bits, None for Parity, and 1 for Stop Bits).
5. From the Property windows Terminal page, select ANSI or VT100 for Terminal Type and then click OK.
6. If you are using the OnCell G3100, you may power it up at this point and hold down the “grave accent key”
(`) while powering it up, as shown below. Note that the grave accent key (sometimes called “backwards
apostrophe”) is NOT the apostrophe keyit is the key usually found next to the number 1 key.