Sagi FD70LT [102/219] Negative temperature 20 10 c 22 15 c 48c

Sagi FD70LT [102/219] Negative temperature 20 10 c 22 15 c 48c
10
2=the defrost will be activated when the evaporator temperature will have remained below
the tem-perature d9 the time d0 (8)
d9
-99
99
°C/°F (1)
0
evaporator temperature above which the count of the defrost interval is suspended (only if
d8 = 2)
dA
0
99
min
0
minimum time the compressor must be remained turned on (to the defrost activation) in
order that thedefrost can be activated (only if d1 = 1) (9)
LABEL
MIN.
MAS.
U.M.
DEF.
TEMPERATURE ALARMS
A0
0
2
-
0
temperature joined to the lower temperature alarm
0=cabinet temperature
1=evaporator temperature (10)
A1
-99
99
°C/°F (1)
-2
temperature below which the lower temperature alarm is activated; also look at A0 and A2
(4)
A2
0
2
-
1
kind of lower temperature alarm
0=alarm not enabled
1=relative to the working setpoint (or "working setpoint
- A1”; consider A1 without sign)
2=absolute (or A1)
A4
-99
99
°C/°F (1)
15
temperature above which the upper temperature alarm is activated; also look at A3 and
A5 (4)
A5
0
2
-
1
kind of upper temperature alarm
0=alarm not enabled
1=relative to the working setpoint (or "working setpoint + A4”; consider A4 without sign)
2=absolute (or A4)
A6
0
240
min
120
upper temperature alarm delay since you turn on the instrument (only if A3 = 0)
A7
0
240
min
15
temperature alarm delay
A8
0
240
min
60
upper temperature alarm delay since the end of the after dripping evaporator fan delay
(only if A3 = 0)(12)
LABEL
MIN.
MAS.
U.M.
DEF.
EVAPORATOR FAN
F0
0
4
-
1
evaporator fan activity during the normal operation
0=turned off
1=turned on
2=according to the compressor
3=according to F1 (14)
4=turned off if the compressor is turned off, according to F1 if the compressor is turned on
(14)
F1
-99
99
°C/°F (1)
-1
evaporator temperature above which the evaporator fan is turned off
(only if F0 = 3 or 4) (4)
F2
0
2
-
0
evaporator fan activity during the defrost and the dripping
0=turned off
1=turned on
2=according to F0
F3
0
15
min
3
duration of the after dripping evaporator fan delay
LABEL
MIN.
MAS.
U.M.
DEF.
SERIAL NETWORK (MODBUS)
LA
1
247
-
1
instrument address
Lb
0
3
-
2
baud rate
0=2.400 baud
1=4.800 baud
2=9.600 baud
3=19.200 baud
LP
0
2
-
2
parity
0=none
1=odd
2=even
(1) the unit of measure depends on parameter P2
(2) set the parameters related to the regulators appropriately after the modification of the parameter P2
(3) if parameter C1 has value 0, the delay since the end of the cabinet probe error will however be 2 min
(4) the differential of the parameter is 2.0 °C/4 °F
(6) the instrument stores the count of the defrost interval every 30 min; the modification of parameter d0 has effect since the end of the previousdefrost interval or since
the activation of a defrost by hand
(7) the display restores the normal operation as soon as the after dripping evaporator fan delay ends and the cabinet temperature falls belowthe one that has locked the
display (or if a temperature alarm arises)
(8) if parameter P3 has value 0 or 2, the instrument will work as if parameter d8 had value 0
(9) if (to the defrost activation) the duration of the activation of the compressor is shorter than the time you have set with parameter dA, thecompressor will further
remain turned on the fraction of time required to complete it
(10) if parameter P3 has value 0, the instrument will work as if parameter A0 had value 0
(12) during the defrost, the dripping and the evaporator fan delay the temperature alarms are not enabled, on condition that they have arisenafter the activation of the
defrost
(14) if parameter P3 has value 0, the instrument will work as if parameter F0 had value 2
NEGATIVE TEMPERATURE -20/-10°C; -22/-15°C(48c)
Setting the working setpoint
x make sure the keyboard is not locked and no procedure is running
x press
LED will flash
x press
or , within 15 seconds to change the temperature value.
x after changing the value, confirm by pressing
, or avoiding any operation for 15 seconds.
You also can modify the working setpoint through parameter SP.