11
Working setpoints
LABEL
MIN.
MAS.
U.M.
DEF.
-20/-10
DEF.
-22/-15
WORKING SETPOINTS
r1
r2
°C/°F (1)
-20
-20
working setpoint
Setting configuration parameters
To gain access the procedure:
x make sure no procedure is running
x press
and 4 s: the display will show “PA
x press
x press
or in 15 s to set “-19
x press
or do not operate 15 s
x press
and 4 s: the display will show “SP
To select a parameter:
x press or
To modify a parameter:
x press
x press
or in 15 s
x press
or do not operate 15 s.
To quit the procedure:
x press and 4 s or do not operate 60 s.
Parametri di configurazione
LABEL
MIN.
MAS.
U.M.
DEF.
-20/-10
DEF.
-22/-15
WORKING SETPOINTS
SP
r1
r2
°C/°F (1)
-20
-20
working setpoint
LABEL
MIN.
MAS.
U.M.
DEF.
-20/-10
DEF.
-22/-15
MEASURE INPUTS
CA1
-25
25
°C/°F (1)
-1
-2
cabinet probe offset
CA2
-25
25
°C/°F (1)
0
0
evaporator probe offset
CA3
-25
25
°C/°F (1)
0
0
auxiliary probe offset (only if P4 = 1 or 2)
P0
0
1
-
1
1
kind of probe (0=PTC, 1=NTC)
P1
0
1
-
0
0
decimal point Celsius degree (for the quantity to show during the normal operation) (1=
YES)
P2
0
1
-
0
0
unit of measure temperature (2) (0=°C, 1=°F)
P3
0
2
-
1
1
evaporator probe function
0=probe not enabled
1=defrost probe and the
rmostat probe for the evaporator fan
2=thermostat probe for the evaporator fan
P4
0
3
-
0
0
fourth input function0 = no probe
1 = sensor input (auxiliary probe, display probe)
2 = sensor input (auxiliary probe, condenser probe)
3 = digital input (multifunction input)
P5
0
4
-
0
0
quantity to show during the normal operation
0=cabinet temperature
1=working setpoint
2=evaporator temperature
3=“cabinet temperature - evaporator temperature”
P6
0
4
-
0
0
quantity displayed by the remote indicator
0 = cabinet
temperature
1 = operational setpoint
2 = evaporator temperature
3 = "cabinet temperature
- evaporator temperature"
4 = temperature detected by the auxiliary probe (only if P4 = 1 or 2)
LABEL
MIN.
MAS.
U.M.
DEF.
-20/-10
DEF.
-22/-15
MAIN REGULATOR
r0
0.1
15
°C/°F (1)
2
2
working setpoint differential
r1
-99
r2
°C/°F (1)
-20
-22
minimum working setpoint
r2
r1
99
°C/°F (1)
-10
-15
maximum working setpoint
r3
0
1
-
0
0
locking the working setpoint modification (1= YES)
r4
0
99
°C/°F (1)
0
0
temperature increase during Energy Saving function (only if P4 = 3 and i5 = 2 or 3)
LABEL
MIN.
MAS.
U.M.
DEF.
-20/-10
DEF.
-22/-15
COMPRESSOR PROTECTIONS (3)
C0
0
240
min
0
0
compressor delay since you turn on the instrument (4)
C1
0
240
min
5
5
minimum time between two activations in succession of the compressor; also
compressor delay sincethe end of the cabinet probe error (5) (6)
C2
0
240
min
3
3
minimum time the compressor remains turned off (5)
C3
0
240
s
10
10
minimum time the compressor remains turned on
C4
0
240
min
10
10
time the compressor remains turned off during the cabinet probe error; also look at C5
C5
0
240
min
10
10
time the compressor remains turned on during the cabinet probe error; also look at C4