Airwell K 45 OG [4/16] Condensate pump

Airwell K 45 OG [4/16] Condensate pump
Page 4
Electrical Data
MODELS 30 45
Power supply ~230 V - 50 Hz
* *
VENTILATION
Nominal current A 0.9 0.96
Maximum current A 1.27 1.35
Fuse rating aM
* A 2 2
Fuse rating ASE/VDE
* A 2 2
Cable section mm
2
3G 1.5 3G 1.5
VENTILATION + ELECTRIC HEATING
Nominal current A 19.0
Maximum current A 22.6
Fuse rating aM
* A 25
Fuse rating ASE/VDE
* A 25
Cable section mm
2
3G 4
MODELS 30 45
Power supply 3 N ~400 V - 50 Hz
* *
VENTILATION + ELECTRIC HEATING
Nominal current A 7.4 11.2
Maximum current A 8.5 15
Fuse rating aM
* A 10 16
Fuse rating ASE/VDE
* A 10 16
Cable section mm
2
5G 1.5 5G 1.5
* These values are given for information only, they should be checked and adjusted according to standards in force : they depend on the mode
of installation and the type of wires selected.
Condensate Pump
PUMP DATA
Nominal voltage 1 ~ 230 V - 50 Hz
Power input
W 16
Current input A 0.12
Waterflow max.
l/h 240
Max. manometric head mWG 0.5
Electric Heating
Electric heating capacity
The electric heating of the cassettes is composed of heating
resistances placed inside the tubes of the heat exchanger.
These resistances are heat protected against any abnormal
temperature rise by two thermostats equipped with a "positive safety"
device (mechanical or thermic destruction of the capillary switches
off the heating permanently) :
- a thermostat with automatic reset,
- a thermostat with manual reset.
Standard models 30
Capacity 4300 W
Standard models 30 45
Capacity 4300 W 5400 W
Power supply : 230 V - 50 Hz
Power supply : 3 N ~ 400 V - 50 Hz