Summer performances Size : RT4D 40
Outdoor air percentage = 40% Outdoor temperature (dry bulb °C)
Indoor conditions (Dry bulb °C / Wet bulb °C)
25 30 32 35 38 40
24 °C / 18 °C
Cooling capacity (kW) 29.5 28.6 28.3 27.6 27.0 26.6
Compressors power input (kW) 5.25 5.93 6.23 7.00 7.20 7.49
26 °C / 19.5 °C
Cooling capacity (kW) 31.1 30.1 29.8 29.2 28.4 27.9
Compressors power input (kW) 5.35 6.03 6.32 6.91 7.30 7.59
29 °C / 22 °C
Cooling capacity (kW) 33.7 32.7 32.2 31.6 30.9 30.3
compressors power input (kW) 5.45 6.13 6.42 7.20 7.39 7.68
31 °C / 24 °C
Cooling capacity (kW) 35.7 34.7 34.3 33.5 32.8 32.2
Compressors power input (kW) 5.45 6.13 6.52 7.20 7.39 7.78
Winter performances Size : RT4D 40
Outdoor air percentage = 40% Outdoor temperature (dry bulb °C)
Indoor conditions (Dry bulb temp. °C / Relative humidity %)
-7 -3 0 3 7 10
16 °C / 40 %
Heating capacity (kW) 18.74 20.03 21.65 23.48 25.96 28.11
Compressors power input (kW) 4.57 4.66 4.92 5.10 5.36 5.62
18 °C / 40 %
Heating capacity (kW) 18.85 20.03 21.76 23.48 25.96 28.11
Compressors power input (kW) 4.83 4.92 5.10 5.36 5.62 5.89
20 °C / 40 %
Heating capacity (kW) 18.85 20.03 21.76 23.59 25.96 28.11
Compressors power input (kW) 5.01 5.18 5.36 5.62 5.98 6.24
22 °C / 40 %
Heating capacity (kW) 18.85 20.14 21.76 23.59 25.96 28.11
Compressors power input (kW) 5.27 5.45 5.62 5.89 6.24 6.50
Summer performances Size : RT4D 40
Outdoor air percentage = 60% Outdoor temperature (dry bulb °C)
Indoor conditions (Dry bulb °C / Wet bulb °C)
25 30 32 35 38 40
24 °C / 18 °C
Cooling capacity (kW) 31.3 30.3 29.9 29.2 28.6 28.2
Compressors power input (kW) 5.21 5.89 6.18 6.95 7.14 7.43
26 °C / 19.5 °C
Cooling capacity (kW) 32.9 31.9 31.5 30.9 30.1 29.6
Compressors power input (kW) 5.31 5.98 6.27 6.85 7.24 7.53
29 °C / 22 °C
Cooling capacity (kW) 35.7 34.6 34.1 33.4 32.7 32.1
Compressors power input (kW) 5.41 6.08 6.37 7.14 7.34 7.63
31 °C / 24 °C
Cooling capacity (kW) 37.8 36.7 36.3 35.4 34.7 34.1
Compressors power input (kW) 5.41 6.08 6.47 7.14 7.34 7.72
Winter performances Size : RT4D 40
Outdoor air percentage = 60% Outdoor temperature (dry bulb °C)
Indoor conditions (Dry bulb temp. °C / Relative humidity %)
-7 -3 0 3 7 10
16 °C / 40 %
Heating capacity (kW) 19.45 20.79 22.47 24.37 26.94 29.18
Compressors power input (kW) 4.37 4.45 4.70 4.87 5.12 5.37
18 °C / 40 %
Heating capacity (kW) 19.57 20.79 22.58 24.37 26.94 29.18
Compressors power input (kW) 4.62 4.70 4.87 5.12 5.37 5.63
20 °C / 40 %
Heating capacity (kW) 19.57 20.79 22.58 24.5 26.94 29.18
Compressors power input (kW) 4.79 4.95 5.12 5.37 5.71 5.96
22 °C / 40 %
Heating capacity (kW) 19.57 20.91 22.58 24.48 26.94 29.18
Compressors power input (kW) 5.04 5.21 5.37 5.63 5.96 6.21