Summer performances Size : RT4D 100
Outdoor air percentage = 0% Outdoor temperature (dry bulb °C)
Indoor conditions (Dry bulb °C / Wet bulb °C)
25 30 32 35 38 40
24 °C / 18 °C
Cooling capacity (kW) 52.8 51 50.3 49.1 47.9 47
Compressors power input (kW) 11.37 12.83 13.45 14.4 15.43 16.1
26 °C / 19.5 °C
Cooling capacity (kW) 55.5 53.6 52.7 51.5 50.3 49.5
Compressors power input (kW) 11.47 12.93 13.56 14.5 15.5 16.27
29 °C / 22 °C
Cooling capacity (kW) 60.2 58 57.1 55.9 54.6 53.7
compressors power input (kW) 11.58 13.03 13.66 14.7 15.75 16.48
31 °C / 24 °C
Cooling capacity (kW) 63.8 61.7 60.8 59.4 58 57
Compressors power input (kW) 11.78 13.25 13.87 14.91 15.96 16.69
Winter performances Size : RT4D 100
Outdoor air percentage = 0% Outdoor temperature (dry bulb °C)
Indoor conditions (Dry bulb temp. °C / Relative humidity %)
-7 -3 0 3 7 10
16 °C / 40 %
Heating capacity (kW) 35.7 37.8 40.7 44.2 49.1 53
Compressors power input (kW) 11.3 11.4 11.7 11.9 12.4 12.7
18 °C / 40 %
Heating capacity (kW) 35.7 37.8 40.7 44.1 49.1 52.9
Compressors power input (kW) 11.7 11.9 12.1 12.4 12.9 13.2
20 °C / 40 %
Heating capacity (kW) 35.6 37.8 40.7 44.1 49 52.8
Compressors power input (kW) 12.2 12.4 12.6 12.8 13.4 13.8
22 °C / 40 %
Heating capacity (kW) 35.7 37.8 40.7 44.1 48.9 52.7
Compressors power input (kW) 12.7 12.9 13.2 13.5 14 14.4
Summer performances Size : RT4D 100
Outdoor air percentage = 25% Outdoor temperature (dry bulb °C)
Indoor conditions (Dry bulb °C / Wet bulb °C)
25 30 32 35 38 40
24 °C / 18 °C
Cooling capacity (kW) 57.2 55.2 54.5 53.2 51.9 50.9
Compressors power input (kW) 11.06 12.48 13.08 14.01 15.01 15.66
26 °C / 19.5 °C
Cooling capacity (kW) 60.1 58.0 57.1 55.8 54.5 53.6
Compressors power input (kW) 11.16 12.58 13.19 14.1 15.08 15.83
29 °C / 22 °C
Cooling capacity (kW) 65.2 62.8 61.8 60.5 59.1 58.2
Compressors power input (kW) 11.26 12.68 13.29 14.30 15.32 16.03
31 °C / 24 °C
Cooling capacity (kW) 69.1 66.8 65.8 64.3 62.8 61.7
Compressors power input (kW) 11.46 12.89 13.49 14.50 15.53 16.24
Winter performances Size : RT4D 100
Outdoor air percentage = 25% Outdoor temperature (dry bulb °C)
Indoor conditions (Dry bulb temp. °C / Relative humidity %)
-7 -3 0 3 7 10
16 °C / 40 %
Heating capacity (kW) 37.56 39.77 42.82 46.50 51.65 55.76
Compressors power input (kW) 10.24 10.34 10.61 10.79 11.24 11.51
18 °C / 40 %
Heating capacity (kW) 37.56 39.77 42.82 46.39 51.65 55.65
Compressors power input (kW) 10.61 10.79 10.97 11.24 11.70 11.97
20 °C / 40 %
Heating capacity (kW) 37.45 39.77 42.82 46.4 51.55 55.55
Compressors power input (kW) 11.06 11.24 11.42 11.60 12.15 12.51
22 °C / 40 %
Heating capacity (kW) 37.56 39.77 42.82 46.39 51.44 55.44
Compressors power input (kW) 11.51 11.70 11.97 12.24 12.69 13.06
Units Performance Data - RT4D 100