Summer performances Size : RT4D 180
Outdoor air percentage = 40% Outdoor temperature (dry bulb °C)
Indoor conditions (Dry bulb °C / Wet bulb °C)
25 30 32 35 38 40
24 °C / 18 °C
Cooling capacity (kW) 105.6 102.4 100.9 98.7 96.4 94.9
Compressors power input (kW) 19.29 21.38 22.29 23.84 25.39 26.57
26 °C / 19.5 °C
Cooling capacity (kW) 111.2 107.7 106.2 103.9 101.6 99.9
Compressors power input (kW) 19.47 21.66 22.66 24.1 25.75 26.93
29 °C / 22 °C
Cooling capacity (kW) 120.4 116.8 115.3 112.9 110.4 108.7
compressors power input (kW) 19.93 22.11 23.11 24.66 26.39 27.57
31 °C / 24 °C
Cooling capacity (kW) 128.3 124.4 122.8 120.2 117.6 115.7
Compressors power input (kW) 20.29 22.57 23.57 25.11 26.84 28.12
Winter performances Size : RT4D 180
Outdoor air percentage = 40% Outdoor temperature (dry bulb °C)
Indoor conditions (Dry bulb temp. °C / Relative humidity %)
-7 -3 0 3 7 10
16 °C / 40 %
Heating capacity (kW) 70.57 73.26 77.47 82.98 91.50 98.40
Compressors power input (kW) 17.37 17.55 17.82 18.18 18.81 19.35
18 °C / 40 %
Heating capacity (kW) 70.78 73.48 77.58 83.08 91.50 98.40
Compressors power input (kW) 18.09 18.27 18.54 18.90 19.53 20.16
20 °C / 40 %
Heating capacity (kW) 71.00 73.70 77.80 83.2 91.50 98.30
Compressors power input (kW) 18.81 18.99 19.26 19.8 20.34 20.97
22 °C / 40 %
Heating capacity (kW) 71.21 73.80 77.90 83.30 91.50 98.19
Compressors power input (kW) 19.53 19.71 20.07 20.43 21.24 21.87
Summer performances Size : RT4D 180
Outdoor air percentage = 60% Outdoor temperature (dry bulb °C)
Indoor conditions (Dry bulb °C / Wet bulb °C)
25 30 32 35 38 40
24 °C / 18 °C
Cooling capacity (kW) 112.1 108.7 107.1 104.7 102.3 100.7
Compressors power input (kW) 19.20 21.29 22.19 23.73 25.27 26.45
26 °C / 19.5 °C
Cooling capacity (kW) 118.0 114.3 112.7 110.3 107.9 106.1
Compressors power input (kW) 19.38 21.56 22.55 24.0 25.63 26.81
29 °C / 22 °C
Cooling capacity (kW) 127.8 123.9 122.4 119.8 117.2 115.4
Compressors power input (kW) 19.84 22.01 23.01 24.55 26.27 27.45
31 °C / 24 °C
Cooling capacity (kW) 136.1 132.0 130.3 127.6 124.8 122.9
Compressors power input (kW) 20.20 22.46 23.46 25.00 26.72 27.99
Winter performances Size : RT4D 180
Outdoor air percentage = 60% Outdoor temperature (dry bulb °C)
Indoor conditions (Dry bulb temp. °C / Relative humidity %)
-7 -3 0 3 7 10
16 °C / 40 %
Heating capacity (kW) 72.92 75.71 80.06 85.74 94.55 101.69
Compressors power input (kW) 16.58 16.75 17.01 17.35 17.96 18.47
18 °C / 40 %
Heating capacity (kW) 73.14 75.93 80.17 85.86 94.55 101.69
Compressors power input (kW) 17.27 17.44 17.70 18.04 18.64 19.24
20 °C / 40 %
Heating capacity (kW) 73.37 76.15 80.39 86.0 94.55 101.58
Compressors power input (kW) 17.96 18.13 18.38 18.9 19.42 20.02
22 °C / 40 %
Heating capacity (kW) 73.59 76.27 80.50 86.08 94.55 101.47
Compressors power input (kW) 18.64 18.81 19.16 19.50 20.27 20.88