Airwell RT4D 180 [19/56] Units performance data rt4d 100 continued

Airwell RT4D 60 [19/56] Units performance data rt4d 100 continued
Page 19
Summer performances Size : RT4D 100
Outdoor air percentage = 40% Outdoor temperature (dry bulb °C)
Indoor conditions (Dry bulb °C / Wet bulb °C)
25 30 32 35 38 40
24 °C / 18 °C
Cooling capacity (kW) 59.9 57.8 57.0 55.7 54.3 53.3
Compressors power input (kW) 10.99 12.40 13.00 13.91 14.91 15.56
26 °C / 19.5 °C
Cooling capacity (kW) 62.9 60.8 59.8 58.4 57.0 56.1
Compressors power input (kW) 11.08 12.49 13.10 14.0 14.98 15.72
29 °C / 22 °C
Cooling capacity (kW) 68.3 65.8 64.8 63.4 61.9 60.9
compressors power input (kW) 11.19 12.59 13.20 14.20 15.22 15.92
31 °C / 24 °C
Cooling capacity (kW) 72.3 70.0 68.9 67.4 65.8 64.6
Compressors power input (kW) 11.38 12.80 13.40 14.41 15.42 16.13
Winter performances Size : RT4D 100
Outdoor air percentage = 40% Outdoor temperature (dry bulb °C)
Indoor conditions (Dry bulb temp. °C / Relative humidity %)
-7 -3 0 3 7 10
16 °C / 40 %
Heating capacity (kW) 38.77 41.05 44.20 48.00 53.32 57.56
Compressors power input (kW) 9.89 9.98 10.25 10.42 10.86 11.12
18 °C / 40 %
Heating capacity (kW) 38.77 41.05 44.20 47.89 53.32 57.45
Compressors power input (kW) 10.25 10.42 10.60 10.86 11.30 11.56
20 °C / 40 %
Heating capacity (kW) 38.66 41.05 44.20 47.9 53.21 57.34
Compressors power input (kW) 10.68 10.86 11.03 11.2 11.73 12.08
22 °C / 40 %
Heating capacity (kW) 38.77 41.05 44.20 47.89 53.11 57.23
Compressors power input (kW) 11.12 11.30 11.56 11.82 12.26 12.61
Summer performances Size : RT4D 100
Outdoor air percentage = 60% Outdoor temperature (dry bulb °C)
Indoor conditions (Dry bulb °C / Wet bulb °C)
25 30 32 35 38 40
24 °C / 18 °C
Cooling capacity (kW) 63.4 61.2 60.4 58.9 57.5 56.4
Compressors power input (kW) 10.83 12.22 12.81 13.71 14.70 15.33
26 °C / 19.5 °C
Cooling capacity (kW) 66.6 64.3 63.2 61.8 60.4 59.4
Compressors power input (kW) 10.92 12.31 12.91 13.8 14.76 15.50
29 °C / 22 °C
Cooling capacity (kW) 72.2 69.6 68.5 67.1 65.5 64.4
Compressors power input (kW) 11.03 12.41 13.01 14.00 15.00 15.70
31 °C / 24 °C
Cooling capacity (kW) 76.6 74.0 73.0 71.3 69.6 68.4
Compressors power input (kW) 11.22 12.62 13.21 14.20 15.20 15.90
Winter performances Size : RT4D 100
Outdoor air percentage = 60% Outdoor temperature (dry bulb °C)
Indoor conditions (Dry bulb temp. °C / Relative humidity %)
-7 -3 0 3 7 10
16 °C / 40 %
Heating capacity (kW) 40.38 42.75 46.03 49.99 55.53 59.94
Compressors power input (kW) 9.36 9.44 9.69 9.86 10.27 10.52
18 °C / 40 %
Heating capacity (kW) 40.38 42.75 46.03 49.88 55.53 59.83
Compressors power input (kW) 9.69 9.86 10.02 10.27 10.69 10.94
20 °C / 40 %
Heating capacity (kW) 40.26 42.75 46.03 49.9 55.42 59.72
Compressors power input (kW) 10.11 10.27 10.44 10.6 11.10 11.43
22 °C / 40 %
Heating capacity (kW) 40.38 42.75 46.03 49.88 55.31 59.60
Compressors power input (kW) 10.52 10.69 10.94 11.18 11.60 11.93
Units Performance Data - RT4D 100 (continued)