Airwell RT4D 180 [20/56] Units performance data rt4d 140

Airwell RT4D 60 [20/56] Units performance data rt4d 140
Page 20
Summer performances Size : RT4D 140
Outdoor air percentage = 0% Outdoor temperature (dry bulb °C)
Indoor conditions (Dry bulb °C / Wet bulb °C)
25 30 32 35 38 40
24 °C / 18 °C
Cooling capacity (kW) 75.1 72.7 71.7 70.2 68.4 67.1
Compressors power input (kW) 16.3 18.3 19.2 20.6 22 23
26 °C / 19.5 °C
Cooling capacity (kW) 79.1 76.6 75.5 73.7 71.9 70.7
Compressors power input (kW) 16.5 18.5 19.4 20.8 22.3 23.3
29 °C / 22 °C
Cooling capacity (kW) 85.8 82.9 81.7 79.8 77.9 76.6
compressors power input (kW) 16.8 18.9 19.8 21.2 22.7 23.8
31 °C / 24 °C
Cooling capacity (kW) 91.1 88.1 86.8 84.9 82.8 81.4
Compressors power input (kW) 17 19.2 20.1 21.5 23.1 24.1
Winter performances Size : RT4D 140
Outdoor air percentage = 0% Outdoor temperature (dry bulb °C)
Indoor conditions (Dry bulb temp. °C / Relative humidity %)
-7 -3 0 3 7 10
16 °C / 40 %
Heating capacity (kW) 51.9 54.4 58.1 63 70 75.6
Compressors power input (kW) 14.9 15.1 15.4 15.9 16.6 17.2
18 °C / 40 %
Heating capacity (kW) 51.9 54.4 58.2 63 70 75.5
Compressors power input (kW) 15.5 15.8 16.2 16.7 17.4 18
20 °C / 40 %
Heating capacity (kW) 51.9 54.4 58.2 63.0 70 75.4
Compressors power input (kW) 16.3 16.5 16.9 17.4 18.2 18.9
22 °C / 40 %
Heating capacity (kW) 51.9 54.5 58.3 63 69.9 75.3
Compressors power input (kW) 17 17.3 17.6 18.3 19.1 19.7
Summer performances Size : RT4D 140
Outdoor air percentage = 25% Outdoor temperature (dry bulb °C)
Indoor conditions (Dry bulb °C / Wet bulb °C)
25 30 32 35 38 40
24 °C / 18 °C
Cooling capacity (kW) 81.6 79.0 77.9 76.2 74.3 72.9
Compressors power input (kW) 15.60 17.51 18.37 19.71 21.05 22.01
26 °C / 19.5 °C
Cooling capacity (kW) 85.9 83.2 82.0 80.0 78.1 76.8
Compressors power input (kW) 15.79 17.70 18.56 19.9 21.34 22.30
29 °C / 22 °C
Cooling capacity (kW) 93.2 90.0 88.7 86.7 84.6 83.2
Compressors power input (kW) 16.08 18.09 18.95 20.29 21.72 22.78
31 °C / 24 °C
Cooling capacity (kW) 98.9 95.7 94.3 92.2 89.9 88.4
Compressors power input (kW) 16.27 18.37 19.23 20.57 22.11 23.06
Winter performances Size : RT4D 140
Outdoor air percentage = 25% Outdoor temperature (dry bulb °C)
Indoor conditions (Dry bulb temp. °C / Relative humidity %)
-7 -3 0 3 7 10
16 °C / 40 %
Heating capacity (kW) 54.60 57.23 61.12 66.28 73.64 79.53
Compressors power input (kW) 13.96 14.15 14.43 14.90 15.56 16.12
18 °C / 40 %
Heating capacity (kW) 54.60 57.23 61.23 66.28 73.64 79.43
Compressors power input (kW) 14.53 14.81 15.18 15.65 16.31 16.87
20 °C / 40 %
Heating capacity (kW) 54.60 57.23 61.23 66.3 73.64 79.32
Compressors power input (kW) 15.28 15.46 15.84 16.3 17.06 17.71
22 °C / 40 %
Heating capacity (kW) 54.60 57.33 61.33 66.28 73.53 79.22
Compressors power input (kW) 15.93 16.21 16.49 17.15 17.90 18.46