Airwell RT4D 180 [15/56] Units performance data rt4d 60 continued

Airwell RT4D 60 [15/56] Units performance data rt4d 60 continued
Page 15
Summer performances Size : RT4D 60
Outdoor air percentage = 40% Outdoor temperature (dry bulb °C)
Indoor conditions (Dry bulb °C / Wet bulb °C)
25 30 32 35 38 40
24 °C / 18 °C
Cooling capacity (kW) 34.0 32.8 32.4 31.7 30.9 30.5
Compressors power input (kW) 5.99 6.77 7.07 7.56 8.15 8.54
26 °C / 19.5 °C
Cooling capacity (kW) 35.9 34.6 34.2 33.4 32.6 32.2
Compressors power input (kW) 6.08 6.77 7.16 7.80 8.24 8.64
29 °C / 22 °C
Cooling capacity (kW) 39.0 37.8 37.2 36.4 35.5 35.0
compressors power input (kW) 6.18 6.97 7.26 7.75 8.34 8.73
31 °C / 24 °C
Cooling capacity (kW) 41.6 40.2 39.7 38.8 37.9 37.1
Compressors power input (kW) 6.18 6.97 7.36 7.85 8.44 8.83
Winter performances Size : RT4D 60
Outdoor air percentage = 40% Outdoor temperature (dry bulb °C)
Indoor conditions (Dry bulb temp. °C / Relative humidity %)
-7 -3 0 3 7 10
16 °C / 40 %
Heating capacity (kW) 22.35 23.87 25.72 27.90 30.96 33.35
Compressors power input (kW) 5.11 5.30 5.39 5.57 5.84 6.12
18 °C / 40 %
Heating capacity (kW) 22.35 23.87 25.72 27.90 30.85 33.25
Compressors power input (kW) 5.39 5.48 5.66 5.84 6.21 6.39
20 °C / 40 %
Heating capacity (kW) 22.35 23.87 25.72 27.80 30.85 33.25
Compressors power input (kW) 5.66 5.75 5.94 6.30 6.48 6.76
22 °C / 40 %
Heating capacity (kW) 22.45 23.87 25.72 27.80 30.85 33.14
Compressors power input (kW) 5.94 6.03 6.21 6.48 6.76 7.03
Summer performances Size : RT4D 60
Outdoor air percentage = 60% Outdoor temperature (dry bulb °C)
Indoor conditions (Dry bulb °C / Wet bulb °C)
25 30 32 35 38 40
24 °C / 18 °C
Cooling capacity (kW) 36.0 34.8 34.3 33.6 32.8 32.3
Compressors power input (kW) 5.91 6.69 6.98 7.46 8.04 8.43
26 °C / 19.5 °C
Cooling capacity (kW) 38.0 36.7 36.2 35.4 34.5 34.1
Compressors power input (kW) 6.01 6.69 7.07 7.70 8.14 8.53
29 °C / 22 °C
Cooling capacity (kW) 41.3 40.0 39.4 38.6 37.6 37.0
Compressors power input (kW) 6.10 6.88 7.17 7.66 8.24 8.62
31 °C / 24 °C
Cooling capacity (kW) 44.0 42.6 42.0 41.1 40.1 39.3
Compressors power input (kW ) 6.10 6.88 7.27 7.75 8.33 8.72
Winter performances Size : RT4D 60
Outdoor air percentage = 60% Outdoor temperature (dry bulb °C)
Indoor conditions (Dry bulb temp. °C / Relative humidity %)
-7 -3 0 3 7 10
16 °C / 40 %
Heating capacity (kW) 23.23 24.81 26.74 29.00 32.18 34.67
Compressors power input (kW) 4.87 5.04 5.13 5.30 5.57 5.83
18 °C / 40 %
Heating capacity (kW) 23.23 24.81 26.74 29.00 32.06 34.56
Compressors power input (kW) 5.13 5.22 5.39 5.57 5.91 6.09
20 °C / 40 %
Heating capacity (kW) 23.23 24.81 26.74 28.9 32.06 34.56
Compressors power input (kW) 5.39 5.48 5.65 6.00 6.17 6.43
22 °C / 40 %
Heating capacity (kW) 23.34 24.81 26.74 28.89 32.06 34.44
Compressors power input (kW) 5.65 5.74 5.91 6.17 6.43 6.70
Units Performance Data - RT4D 60 (continued)