Airwell RoofT@ir 60 [10/68] Electrical specifications

Airwell RoofT@ir 40 [10/68] Electrical specifications
8
INSTALLATION
ELECTRICAL SPECIFICATIONS
IMPORTANT
A main fuse must mandatorily be provided on the power supply.
Fuses not supplied
¢
Cables not supplied ¢
The unit is not designed to withstand weights or stresses from adjacent equipment, pipe work or
constructions. Any foreign weight or stress on the unit structure could lead to a malfunction or a
collapse with dangerous consequences for personnel and property. In such an event, the warranty
shall be null and avoid.
The unit supporting base shall be supplied as indicated in the manual. There could be a risk of
personal injury or damage to property in the event of the unit being incorrectly supported.
The building structure must be capable to carrying the weight of the unit during operation.
¢
The place of installation must not be subject to flooding. ¢
The Rooft@ir should be installed on a flat, clean surface without any obstacles. The surface area ¢
must be sufficient to spread the weight of the unit over the building structure.
Ensure that the recommended free clearances around the unit are maintained to avoid any risk of
¢
malfunctions.
The installer is responsible for providing the weaterproof seal between the building and the Rooft@ir.
¢
The installer must be fully versed in the practice of roof mounted equipments and must comply with
the recommendations and rules detailed in the Technical Directives.
In order to avoid risk of condensation and energy losses, all outdoor ducting and piping must be
¢
insulated.
UNIT WITHOUT HEATING
UNIT WITH HEATING TYPE CH1
PLACE OF INSTALLATION AND REQUIREMENTS
UNIT WITH HEATING TYPE CH2
Models
40 50 60 70 80 100 110
PE GE PE GE PE GE PE GE PE GE PE GE PE GE
Power supply 3+N /400 /50Hz
Maximum current
A
42 47 49 55 69 73 73 77 101 101 93 99 96 102
Total starting current
A
127 133 142 148 166 170 168 172 239 239 270 276 273 279
Fuse rating FFG aM
A
50 50 50 63 80 80 80 80 125 125 100 100 100 100
Models
40 50 60 70 80 100 110
PE GE PE GE PE GE PE GE PE GE PE GE PE GE
Power supply 3+N /400 /50Hz
Capacities KW 21 21 36 36 36 36 36
Maximum current
A
72 77 79 85 121 125 125 129 153 153 145 151 148 154
Total starting current
A
158 163 172 178 218 222 220 224 291 291 322 328 325 331
Fuse rating FFG aM
A
80 80 80 100 125 125 125 160
160 160 160 160 160 160
Models
40 50 60 70 80 100 110
PE GE PE GE PE GE PE GE PE GE PE GE PE GE
Power supply 3+N /400 /50Hz
Capacities KW 31.5 31.5 48 48 48 48 48
Maximum current
A
87 92 94 100 138 142 142 146 170 170 162 169 165 172
Total starting current
A
173 178 187 193 235 239 237 241 308 308 339 346 342 349
Fuse rating FFG aM
A
100 100 100 100 160 160 160 160
200 200 200 200 200 200

Содержание