Airwell SLH 1402 [13/40] Physical data slh 2402 to 3804 eln version

Airwell SLH 2202 [13/40] Physical data slh 2402 to 3804 eln version
Page 13
Physical Data SLH 2402 to 3804 - ELN Version
(1) Data based on leaving chilled water temperature of 7 °C and ambient air temperature of 35 °C.
(2) Data based on leaving hot water temperature of 45 °C and ambient air temperature of 7 °C/88 % HR.
(3) Data given for compressors only.
(4) Sound levels given at fully loaded conditions. Sound power level values refer to ISO 3744 and Eurovent 8/1.
(5) Sound pressure level values refer to ISO 3744.
SLH ELN models 2402 2602 2804 3204 3604 3804
Nominal cooling capacity (1) kW 458.4 493.8 552.0 630.6 679.7 726.9
Power input (3) kW 192.5 215.5 233.4 263.4 292.0 315.1
EER 2.4 2.3 2.4 2.4 2.3 2.3
Nominal heating capacity (2) kW 507.0 543.0 600.4 683.4 745.6 823.7
Power input (3) kW 185.7 189.5 211.8 237.6 264.6 292.4
COP 2.7 2.9 2.8 2.9 2.8 2.8
Number of refrigerant circuits 224444
Number of capacity steps
Compressors
Number 224444
Type
Evaporators
Number 112222
Type
Water content per evaporator litres 50 50 26/26 33/33 40/40 40/40
Condensers
Number of coils 448888
Face area per coil m
2
668888
Number of rows 454444/5
Fans
Number of fans 10 10 12 16 16 16
Nominal fan speed rpm 500 500 500 500 550 550
Total air flow m
3
/h 102 000 97 000 124 000 150 000 163 800 158 000
Total power kW 12.5 12.5 15.0 20.0 20.0 20.0
Weight
Shipping weight kg 6280 6510 8320 8540 8560 9380
Operating weight kg 6330 6560 8373 8606 8640 9460
Sound levels
Sound power levels (4) dB(A) 89.0 89.0 91.0 92.0 92.0 92.0
Sound pressure levels at 10 m (5) dB(A) 56.7 56.7 59.0 60.0 60.0 60.0
Dimensions
Length mm 6030 6030 8400 8400 8400 8400
Width mm220022002200220022002200
Height mm 2550 2550 2550 2550 2550 2550
Twin screw
Plate
612