Airedale Ultima Compact UCC 300 [20/53] Ultima compact chillers

Airedale Ultima Compact UCC 200 [20/53] Ultima compact chillers
ULTIMA COMPACT Chillers
Chillers
20
Installation & Maintenance : 903-129 IM E 10/04/C
Installation Data
WATER SYSTEM
UCC160D-4/2 UCC180D-6/2 UCC200D-6/2 UCC225D-6/2 UCC250D-6/2 UCC275D-8/2
Connections
Water Inlet / Outlet (1) DN 80 DN 80 DN 80 DN 80 DN 80 DN 100
Water Drain/Bleed in 1/2 1/2 1/2 1/2 1/2 1/2
Water System
Min. System Water Volume (2) l 802 669 736 820 1304 877
Max. System Press Bar 10 10 10 10 10 10
OPTIONAL EXTRAS - ALL MODELS
Water Pump (3) In Line Pump
Nom External Head Std Single / R&S kPa 115 100 100 100 95 97
Nom External Head Larger Single/R&S kPa 170 156 155 150 149 160
Nom External Head Standard Twin kPa 115 100 99 93 87 95
Nom External Head Larger Twin kPa 167 150 148 142 137 158
Expansion Tank (4)
Water Capacity l 50 50 50 50 50 50
Buffer Tank (6)
Max. Water Capacity - D l 250 250 250 250 250 420
Max. Water Capacity - SQ/DQ l 250 250 250 420 420 420
Max. Water Capacity - SSQ/DSQ l 250 420 420 420 420 420
Pressurisation Unit
Water Inlet Connection in 1/2 1/2 1/2 1/2 1/2 1/2
UCC300D-8/2 UCC330D-10/2 UCC360D-10/2 UCC400D-12/2 UCC450D-12/2
Connections
Water Inlet / Outlet (1) DN 100 DN 100 DN 100 DN 100 DN 100
Water Drain/Bleed in 1/2 1/2 1/2 1/2 1/2
Water System
Min. System Water Volume (2) l 897 1130 1122 1322 1348
Max. System Press Bar 10 10 10 10 10
OPTIONAL EXTRAS - ALL MODELS
Water Pump (3) In Line Pump
Nom External Head Std Single / R&S kPa 98 137 135 128 125
Nom External Head Larger Single/R&S kPa 162 158 156 151 181
Nom External Head Standard Twin kPa 127 119 115 105 127
Nom External Head Larger Twin kPa 160 156 154 148 175
Expansion Tank (4)
Water Capacity l 50 50 50 50 50
Buffer Tank (5)
Max. Water Capacity - D l 420 420 420 420 420
Max. Water Capacity - SQ/DQ l 420 420 420 420 420
Max. Water Capacity - SSQ/DSQ l 420 420 420 420 420
Pressurisation Unit
Water Inlet Connection in 1/2 1/2 1/2 1/2 1/2
(1) Flanged to PN16.
(2) For minimum system volume refer to the Technical Manual.
(3) Nominal Cooling Duties based on 12/7°C water temperature and 30°C ambient, where output is the chilled water duty and input is the compressor input power.
(4) Expansion vessel may require reselecting for glycol and system volume, please refer to Airedale
(5) 8 Fan units only: Maximum Water Capacity becomes 250 litres when the pump option is also selected.