Airedale Ultima Compact UCC 300 [26/53] Ultima compact chillers

Airedale Ultima Compact UCC 360 [26/53] Ultima compact chillers
ULTIMA COMPACT Chillers
Chillers
26
Installation & Maintenance : 903-129 IM E 10/04/C
Installation Data
ELECTRICAL DATA
UCC75D-2/1 UCC100D-2/1 UCC110D-4/2 UCC125D-3/1 UCC130D-4/2 UCC150D-3/1
Unit Data
Nominal Run Amps (1) A 50 62 69 79 84 93
Maximum Start Amps (2) A 140 167 175 217 222 246
Permanent Supply VAC 230 V 1 PH 50 Hz
Mains Supply VAC 400 V 3 PH 50 Hz
Rec Permanent Fuse Size A 16 16 16 16 16 16
Rec Mains Fuse Size A 63 80 100 125 125 125
Max Permanent Incoming Cable Size mm² 4 mm² terminals
Max Mains Incoming Cable Size mm² 70 (Direct to
MCCB)
70 (Direct to
MCCB)
Direct to Bus Bar
70 (Direct to
MCCB)
Direct to Bus Bar
70 (Direct to
MCCB)
Control Circuit VAC 24V/230V AC
Evaporator
Pad Heater Rating W 40 40 80 80 80 80
External Trace Heating
Available (fitted by others) W 500 500 500 500 500 500
Condenser Fan - Per Fan
Quantity 2 2 4 3 4 3
Full Load Amps A 1.75 1.75 2.70 1.75 2.70 1.75
Locked Rotor Amps A 6.20 6.20 7.00 6.20 7.00 6.20
Motor Rating kW 0.98 0.98 1.60 0.98 1.60 0.98
Compressor - Per Compressor
Quantity 4 4 4 2 + 2 2 + 2 4
Motor Rating kW 6.2 8.1 8.1 8.1 / 11.7 8.1 / 11.7 11.7
Nominal Run Amps (1) A 11.7 14.6 14.6 14.6 / 22.0 14.6 / 22.0 22.0
Sump Heater Rating W 65.0 65.0 65.0 65.0 / 75.0 65.0 / 75.0 75.0
Start Amps (2) 98.0 120.0 120.0 120.0/ 175.0 120.0/ 175.0 175.0
Type Of Start Direct on line
QUIET DQ UCC75DQ-2/1 UCC100DQ-3/1 UCC110DQ-4/2 UCC125DQ-3/1 UCC130DQ-4/2 UCC150DQ-4/1
All data as above except:
Condenser Fan - Per Fan
Quantity 2 3 4 3 4 4
Full Load Amps A 1.15 1.15 1.25 1.15 1.25 1.15
Locked Rotor Amps A 2.10 2.10 4.50 2.10 4.50 2.10
Motor Rating kW 0.68 0.68 0.69 0.68 0.69 0.68
SUPER QUIET DSQ UCC75DSQ-2/1 UCC100DSQ-3/1 UCC110DSQ-4/2 UCC125DSQ-4/1 UCC130DSQ-6/2 UCC150DSQ-4/1
All data as above except:
Condenser Fan - Per Fan
Quantity 2 3 4 4 6 4
Full Load Amps A 0.83 0.83 0.78 0.83 0.78 0.83
Locked Rotor Amps A 1.50 1.50 1.50 1.50 1.50 1.50
Motor Rating kW 0.32 0.32 0.48 0.32 0.48 0.32
OPTIONAL EXTRAS
Power Factor Correction
Nominal Run Amps (1) A 48 56 63 71 77 85
Maximum Start Amps (2) A 140 167 175 217 222 246
Recommended Mains Fuse A 63 80 100 125 125 125
Compressor Nominal Run Amps
- Per Compressor
A 4 x 11 4 x 13 4 x 13 2 x 20 / 2 x 13 2 x 20 / 2 x 13 4 x 20
Electronic Soft-start
Nominal Run Amps (1) A 50 62 69 79 84 93
Maximum Start Amps (2) A 97 119 132 147 152 176
Recommended Mains Fuse A 63 80 100 125 125 125
Single Head Pump (or Run/Standby)
Unit Nominal Run Amps (1) A 55 67 75 83 90 98
Recommended Mains Fuse A 80 100 100 125 125 160
Motor Rating kW 2.2 2.2 3.0 2.2 3.0 2.2
Full Load Amps
A 4.8 4.8 6.1 4.8 6.1 4.8
Larger Single Head Pump (or Run/Standby)
Unit Nominal Run Amps (1) A 57 69 77 85 92 100
Recommended Mains Fuse A 80 100 100 125 125 160
Motor Rating kW 3.0 3.0 4.0 3.0 4.0 3.0
Full Load Amps
A 6.8 6.8 7.7 6.8 7.7 6.8
Twin Head Pump
Unit Nominal Run Amps (1) A 56 65 75 85 90 99
Recommended Mains Fuse A 80 100 100 125 125 160
Motor Rating kW 3.0 3.0 3.0 3.0 3.0 3.0
Full Load Amps
A 6.1 6.1 6.1 6.1 6.1 6.1
Larger Twin Head Pump
Unit Nominal Run Amps (1) A 58 70 77 86 92 101
Recommended Mains Fuse A 80 100 100 125 125 160
Motor Rating kW 4.0 4.0 4.0 4.0 4.0 4.0
Full Load Amps
A 7.7 7.7 7.7 7.7 7.7 7.7
(1) Based at 12/7°C water and 30°C ambient
(2) Starting amps refers to the direct on line connections.