Maintenance
GENERAL MAINTENANCE
6 MONTHS ACTION NOTES
Repeat 3 month checks plus the following:
SYSTEM Check evaporator trace heating and low ambient thermostat
are set to activate at 4.0ºC.
Remember to re-cap the Schraeder
connections!
12 MONTHS ACTION NOTES
Repeat 6 month checks plus the following:
SYSTEM Check safety devices cut out the compressor at the correct
settings.
Check glycol concentration if appropriate. Adjust as necessary.
Leak test all R407C joints and inspect all water connections. Rectify as necessary.
REFRIGERATION
Check superheats with chiller running on full load (the
height of summer is recommended). Recheck the charge
following major adjustment of the superheats.
Adjust as necessary. A period of 30 minutes
should be allowed between each resetting of the
valve to allow pressures to stabilise.
Thermostatic expansion valve only.
ELECTRICAL Tighten all electrical terminals.
COMPRESSOR
MAINTENANCE
Periodic maintenance and inspection of this equipment is necessary to prevent premature
failure, the following periodic inspections should be carried out by period or hourly use
which ever is sooner.
1 Year
Measure compressor motor insulation.
7,500 Hours or 4 Years
Inspect compressor oil.
For periods of winter shut down the following precautions are recommended:
SHUT DOWN PERIODS
Close the liquid and discharge ball valve
Cap service ports
Turn off electrical circuits
Drain the water from the chiller evaporator via the evaporator drain plug