Installation & Maintenance : 903-129 IM E 10/04/C
Commissioning Procedure
PRE COMMISSIONING CHECKLIST
Check that each circuit trips on low pressure. The alarm should appear within
3 minutes.
The alarm will be recognised at the display circuit trip, to clear the alarms refer
to
Alarm Handling.
CAUTION
Prior to the chiller compressors being allowed to start, the Water Flow Fail and
Pump Interlock features MUST both be proven to work correctly.
To check the water flow fail safety protection is working satisfactorily:
RECORD
Reduce the flow rate to 75% of design and ensure that the evaporator pressure or
flow protection switch trips at this flow rate, adjust as necessary.
With compressors off, ensure this alarm is recognised as “Water Flow Fail” at the
display and disengages the circuits operation immediately. Restore flow rate to the
design and check the alarm has self-cleared.
To check the pump interlock safety feature works satisfactorily:
RECORD
Switch off the chiller water pump and check the interlock wiring connections at the
chiller are open circuit.
To switch the unit OFF, use the microprocessor keypad as follows:
Press
Prg
, press , press , press & finally .
Fully open all liquid line and discharge service ball valves on each circuit.