Daikin FWF04AT [12/19] Capacity tables

Daikin FWF04AT [12/19] Capacity tables
Fan coil units • Ceiling mounted cassette unit • FWF
1
4
• Fan coil units • Ceiling mounted cassette unit • FWF
10
4 Capacity tables
4 - 3 Heating capacity tables
Air temperature (°C DB - °C WB) 20
Water temperature (Entering °C - Leaving °C)
50 - 45 60 - 50 70 - 60
Model
Air Flow
m
3
/hr
Heating
capacity
kW
Water
flow
m
3
/hr
Water
pressure
drop
kPa
Heating
capacity
kW
Water
flow
m
3
/hr
Water
pressure
drop
kPa
Heating
capacity
kW
Water
flow
m
3
/hr
Water
pressure
drop
kPa
FWF02AT
663 3.51 0.60 124.11 3.14 0.27 32.29 3.58 0.31 37.69
630 3.40 0.58 117.36 3.02 0.26 30.50 3.45 0.30 35.56
595 3.28 0.56 109.92 2.88 0.25 28.57 3.29 0.28 33.25
FWF03AT
663 5.40 0.93 110.28 5.03 0.43 26.68 5.66 0.49 31.57
630 5.32 0.91 107.24 4.95 0.43 25.93 5.57 0.48 30.66
595 4.99 0.86 95.28 4.61 0.40 22.96 5.19 0.45 27.12
FWF04AT
731 5.81 1.00 124.16 5.25 0.45 29.46 5.95 0.51 35.35
695 5.46 0.94 111.32 4.90 0.42 26.05 5.56 0.48 31.36
663 5.40 0.93 109.10 4.84 0.42 25.46 5.49 0.47 30.66
Air temperature (°C DB - °C WB) 22
Water temperature (Entering °C - Leaving °C)
50 - 45 60 - 50 70 - 60
Model
Air Flow
m
3
/hr
Heating
capacity
kW
Water
flow
m
3
/hr
Water
pressure
drop
kPa
Heating
capacity
kW
Water
flow
m
3
/hr
Water
pressure
drop
kPa
Heating
capacity
kW
Water
flow
m
3
/hr
Water
pressure
drop
kPa
FWF02AT
663 3.27 0.56 109.15 2.92 0.25 29.11 3.38 0.29 34.61
630 3.17 0.54 103.20 2.81 0.24 27.55 3.25 0.28 32.68
595 3.05 0.52 96.61 2.68 0.23 25.83 3.11 0.27 30.57
FWF03AT
663 5.02 0.86 96.24 4.72 0.41 23.86 5.38 0.46 28.83
630 4.94 0.85 93.59 4.64 0.40 23.20 5.29 0.46 28.01
595 4.64 0.80 83.14 4.32 0.37 20.57 4.93 0.42 24.79
FWF04AT
731 5.38 0.92 108.34 4.90 0.42 26.06 5.63 0.48 32.12
695 5.06 0.87 97.25 4.58 0.39 23.00 5.26 0.45 28.45
663 5.01 0.86 95.31 4.52 0.39 22.47 5.20 0.45 27.81
Heating capacities FWF (2 pipe)