Daikin FWF04AT [13/19] Capacity tables

Daikin FWF04AT [13/19] Capacity tables
3
1
4
• Fan coil units • Ceiling mounted cassette unit • FWF
11
Fan coil units • Ceiling mounted cassette unit • FWF
4 Capacity tables
4 - 4 Capacity correction factor
Heating correction factor
FWF
Entering Air temperature
°C
Entering Water temperature °C
37.8 43.3 45.0 48.8 50.0 54.4 60.0 65.5 70.0 71.1 76.7 82.2 87.7
4.4 1.338 1.376 1.388 1.414 1.422 1.452 1.491 1.529 1.559 1.569 1.605 1.643 1.683
7.2 1.257 1.297 1.310 1.338 1.347 1.379 1.421 1.462 1.497 1.507 1.547 1.586 1.630
10.0 1.176 1.221 1.235 1.265 1.275 1.311 1.356 1.401 1.433 1.444 1.488 1.531 1.577
12.7 1.093 1.140 1.155 1.187 1.198 1.235 1.284 1.331 1.370 1.381 1.426 1.476 1.523
15.5 1.010 1.061 1.077 1.113 1.124 1.165 1.217 1.268 1.306 1.318 1.368 1.420 1.471
18.3 0.958 0.999 1.013 1.044 1.054 1.095 1.149 1.199 1.242 1.255 1.308 1.363 1.419
20.0 0.877 0.933 0.950 0.989 1.000 1.046 1.103 1.159 1.204 1.216 1.274 1.330 1.386
21.1 0.824 0.890 0.910 0.953 0.965 1.014 1.074 1.134 1.179 1.192 1.251 1.308 1.364
23.9 0.758 0.819 0.838 0.880 0.894 0.943 1.005 1.066 1.115 1.129 1.191 1.252 1.312
26.7 0.677 0.741 0.761 0.806 0.820 0.871 0.937 1.001 1.052 1.067 1.133 1.197 1.259