ABB ACH550-01-03A3-4+B055 [12/62] Relay output control

ABB ACH550-01-06A9-4+B055 [12/62] Relay output control
12
Activate Drive Control Functions – EFB
Relay Output Control
Using the fieldbus for relay output control requires:
Drive parameter values set as defined below.
Fieldbus controller supplied reference word(s) in the appropriate location. (The
location is defined by the Protocol Reference, which is protocol dependent.)
1. More than 3 relays requires the addition of a relay extension module.
For example: To control relays 1 and 2 using serial communication:
Set parameters 1401 RELAY OUTPUT 1 and 1402 RELAY OUTPUT 1 = 35 (COMM).
Then, for example using N2:
To turn Relay 1 On: Force object B07 to On.
To turn Relay 2 On: Force object B08 to On.
To turn both Relay 1 and 2 On: Force objects B07 and B08 On.
Note! Relay status feedback occurs without configuration as defined below.
Drive Parameter Value Setting
Protocol Reference
Modbus
N2 FLN
ABB DRV
DCU
PROFILE
1401 RELAY
OUTPUT 1
35
(COMM)
Relay Output 1
controlled by fieldbus.
40134 bit 0 or 00033 BO7 40
1402
RELAY
OUTPUT 2
35
(COMM)
Relay Output 2
controlled by fieldbus.
40134 bit 1 or 00034 BO8 41
1403
RELAY
OUTPUT 3
35
(COMM)
Relay Output 3
controlled by fieldbus.
40134 bit 2 or 00035 BO9 42
1410
1
RELAY
OUTPUT 4
35
(COMM)
Relay Output 4
controlled by fieldbus.
40134 bit 3 or 00036 BO10 43
1411
1
RELAY
OUTPUT 5
35
(COMM)
Relay Output 5
controlled by fieldbus.
40134 bit 4 or 00037 BO11 44
1412
1
RELAY
OUTPUT 6
35
(COMM)
Relay Output 6
controlled by fieldbus.
40134 bit 5 or 00038 BO12 45
Drive
Parameter
Value Setting
Protocol Reference
Modbus
N2 FLN
ABB DRV DCU PROFILE
0122 RO 1-3
STATUS
Relay 1…3 status. 40122 0122 BI4…BI6 76…78
0123
RO 4-6
STATUS
Relay 4…6 status. 40123 0123 BI7…BI9 79…81