Invertek Drives ODV-42075-IN [19/24] Analog and digital input configurations

Invertek Drives ODV-34110-IN [19/24] Analog and digital input configurations
8. Analog and Digital Input Configurations
8.1. Terminal mode (P-12 =0)
P-15 Digital input 1 (T2) Digital input 2 (T3) Digital input 3 (T4) Analog input (T6) Comments
0
Open: Stop (disable)
Closed: Run (enable)
Open : Forward run
Closed : Reverse run
Open : Analog speed
ref
Closed : Preset speed
1
Analog input 1 reference
1
Open: Stop (disable)
Closed: Run (enable)
Open: Analog speed ref
Closed:Preset speed 1/2
Open: Preset speed 1
Closed:Preset speed 2
Analog input 1 reference
Digital Input 2 Digital Input 3 Preset Speed
Open Open Preset Speed 1
Closed Open Preset Speed 2
Open Closed Preset Speed 3
2
Open: Stop (disable)
Closed: Run (enable)
Closed Closed Preset Speed 4
Open: Preset speeds 1-4
Closed:Max Speed(P-01)
4 Preset speeds
selectable.
Analog input used as
digital input Closed status:
8V < Vin < 30V
3
1)
Open: Stop (disable)
Closed: Run (enable)
Open : Analog speed ref
Closed : Preset speed 1
External trip input :
Open: Trip,
Closed: Run
Analog input 1 reference
Connect external
thermistor type PT100 or
similar to digital input 3
4
Open: Stop (disable)
Closed: Run (enable)
Open : Analog input 1
Closed : Analog input 2
Analog input 2
reference
Analog input 1 reference
Switches between analog
inputs 1 and 2
5
Open: Fwd Stop
Closed: Fwd Run
Open: Reverse Stop
Closed: Reverse Run
Open : Analog speed
ref
Closed : Preset speed
1
Analog input 1 reference
Closing digital inputs 1 and
2 together carries out a
fast stop (P-24)
6
1)
Open: Stop (disable)
Closed: Run (enable)
Open : Forward
Closed : Reverse
External trip input :
Open: Trip,
Closed: Run
Analog input 1 reference
Connect external
thermistor type PT100 or
similar to digital input 3
7
Open: Stop (disable)
Closed: Fwd Run (enable)
Open: Stop (disable)
Closed: Rev Run
(enable)
External trip input :
Open: Trip,
Closed: Run
Analog input 1 reference
Closing digital inputs 1 and
2 together carries out a
fast stop (P-24)
Digital Input 3 Analog Input 1 Preset Speed
Open Open Preset Speed 1
Closed Open Preset Speed 2
Open Closed Preset Speed 3
8
Open: Stop (disable)
Closed: Run (enable)
Open : Forward
Closed : Reverse
Closed Closed Preset Speed 4
Digital Input 3 Analog Input 1 Preset Speed
Open Open Preset Speed 1
Closed Open Preset Speed 2
Open Closed Preset Speed 3
9
Open: Stop (disable)
Closed: Forward Run
(enable)
Open: Stop (disable)
Closed: Reverse Run
(enable)
Closed Closed Preset Speed 4
Closing digital inputs 1 and
2 together carries out a
fast stop (P-24)
10
Normally Open (NO)
Momentary close to run
Normally Closed (NC)
Momentary open to stop
Open : Analog speed
ref
Closed:Preset speed 1
Analog input 1 reference
11
Normally Open (NO)
Momentary close to run
Normally Closed (NC)
Momentary open to stop
Normally Open (NO)
Momentary close to
rev
Analog input 1 reference
Closing digital inputs 1 and
3 together carries out a
fast stop (P-24)
12
Open: Stop (disable)
Closed: Run (enable)
Open: Fast Stop
(disable)
Closed: Run (enable)
Open : Analog speed
ref
Closed : Preset speed
1
Analog input 1 reference
NOTE Negative Preset Speeds will be inverted if Run Reverse selected.
Typical Applications
Analog speed input with 1 preset speed
and fwd/rev switch
Analog speed input with 2 preset speeds 4 preset speeds and max speed select
switch. Effectively giving 5 preset speeds
Optidrive E2 IP55/NEMA 12 User Guide
www.invertek.co.uk
19

Содержание

Похожие устройства

Скачать