3. Mechanical Installation
3.1. General
Store the Optidrive in its box until required. Storage should be clean and dry and within the temperature range –40°C to +60°C
Install the Optidrive on a flat, vertical, flame-resistant, vibration-free mounting within a suitable enclosure, according to
EN60529 if specific Ingress Protection ratings are required
The Optidrive must be installed in a pollution degree 1 or 2 environment
The IP55/NEMA 12 drive is intended for INDOOR USE ONLY
Ensure that all terminals are tightened to the appropriate torque setting
3.2. Mechanical dimensions and mounting
A B C D E F G H I J
Drive
Size
mm in mm in mm in mm in mm in mm in mm in mm in mm in mm in
1
200 7.87 166 6.54 - - 141 5.55 33 1.30 162 6.38 140 5.51 128 5.04 4.2 0.17 8.4 0.33
2
310 12.20 276 10.87 - - 251 9.88 33 1.30 176 6.93 164 6.46 153 6.02 4.2 0.17 8.4 0.33
3
310 12.20 276 10.87 - - 251 9.88 33 1.30 228 8.98 210.5 8.29 197.5 7.78 4.2 0.17 8.4 0.33
NOTE
The size 3 product has 4 symmetrical mounting points
Control Terminal Torque Settings of 0.5 Nm (4.5 lb-in) Power Terminal Torque Settings of 1 Nm (9 lb-in)
The IP55 / NEMA 12 Optidrives can be installed side-by-side
with their heatsink flanges touching. This gives adequate
ventilation space between drives.
If the IP55 Optidrive is to be installed above another drive or
any other heat-producing device, the minimum vertical spacing
is 150mm (5.9 inches)