Siemens 6SL3210-1SE31-0AA0 [276/318] Permissible system pressure
Cooling circuit and coolant properties
10.1 Cooling circuit requirements
Manual
276 Manual, 01/2011, 6SL3097-4AC10-0BP2
When the pump is switched on, a (location-dependent) flow pressure is present in the
cooling circuit, which must be determined from the pump characteristic curve and the
volume-flow-dependent pressure drop. Characteristics have been specified for the pressure
drop of the Power Modules. The pressure drop in the filter and, if applicable, an additional
pressure drop in the connection pipes must be added to this pressure drop (70 kPa for H
2
O).
Up to 50 kPa must be added for the pressure drop in a (contaminated) filter and in
connection pipes. The intersection of the pump characteristic curve and the pressure drop of
the whole cooling system yields the volumetric flow V
rated
of the coolant at this operating
point.
S
9
S
9
Q
Q
3XPSFKDUDFWHULVWLFFXUYH
3UHVVXUHGURSLQ
FRROLQJV\VWHP
Figure 10-2 Pump characteristic curve
Permissible system pressure
The maximum permissible system pressure is 600 kPa.
If a pump that is capable of exceeding this maximum permissible system pressure is used,
the customer must take steps (e.g. safety valve p ≤ 600 kPa, pressure control, or similar) to
ensure that the maximum pressure limit is not exceeded.