Siemens 6SL3210-1SE13-1UA0 [294/318] Forming circuit
Service and maintenance
11.3 Forming the DC link capacitors
Manual
294 Manual, 01/2011, 6SL3097-4AC10-0BP2
Forming circuit
The forming circuit can be established using incandescent lamps or alternatively, resistors.
Components required for reforming outside the drive line-up
1 fuse switch, triple 400 V / 10 A or double 230 V / 10 A
Cable 1.5 mm
2
3 incandescent lamps 230 V/100 W for a line voltage of 380 to 480 V 3-ph AC.
Alternatively, use three 1 kΩ / 100 W resistors (e.g. GWK150J1001KLX000 from Vishay)
instead of the incandescent lamps.
2 incandescent lamps 230 V/100 W for a line voltage of 200 to 240 V 1-ph AC.
Alternatively, use 2 1 kΩ / 100 W resistors (e.g. GWK150J1001KLX000 from Vishay)
instead of the incandescent lamps.
Various Small components, such as lamp socket, etc.
DANGER
Dangerously high voltage levels are still present in the cabinet up to 5 minutes after it has
been disconnected due to the DC link capacitors. It is only permissible to work on the
equipment or at the DC link terminals after this time has expired.
0RGXOHWREHIRUPHG
0RWRU
FRQQHFWLRQ
)XVHLVRODWRUV
,QFDQGHVFHQWODPSV
/LQHVXSSO\YROWDJH
3RZHU0RGXOH
3(
:
9
8
3(///
Figure 11-5 Forming circuit for 3-ph AC Power Modules with incandescent lamps