Siemens 6SL3210-1SE16-0UA0 — технические характеристики и параметры силовых модулей [91/318]

Превью страниц Страница 91 / 318
Siemens 6SL3210-1SE14-1UA0 [91/318] Power modules blocksize pm340 3 power modules blocksize pm340
Power Modules
3.1 Power Modules Blocksize (PM340)
Manual
Manual, 01/2011, 6SL3097-4AC10-0BP2
91
Line supply voltage 1-ph. 200 V to 240 V AC ±10%
PM340 6SL3210– 1SB11-0UA0 1SB12-3UA0 1SB14-0UA0
PM340 with integrated line filter 6SL3210– 1SB11-0AA0 1SB12-3AA0 1SB14-0AA0
Circuit breaker type designation
UL489 / CSA C22.2 No. 5-02
Rated current
Rated short-circuit current SCCR
A
kA
5SJ4206-7HG41
6
14
5SJ4210-7HG41
10
14
5SJ4216-7HG41
16
14
Resistance value of the external
braking resistor
Ω > 180 > 180 > 180
Max. cable length to braking
resistor
m 15 15 15
Line supply connection
L, N
Motor connection
U2, V2, W2
DC link connection, connection for
braking resistor DCP/R1, DCN, R2
Screw-type terminals for cable cross-sections 1.0 to 2.5 mm
2
PE connection at the housing with M 4 screw
Max. motor cable length
3)
(without external options)
m 50 (shielded)
75 (unshielded)
Degree of protection IP20 or IPXXB
Weight kg 1.2 1.3 1.3
1) Rated output of a typical standard induction motor at 230 V.
2) The input current depends on the motor load and line impedance. The input currents apply for unit rating loading (based
on I
rated
) for a line impedance corresponding to u
k
= 1%.
3) Max. motor cable length 15 m (shielded) for PM340 Power Modules with integrated line filter to comply with the limit
values of EN 61800-3 Category C2.
Table 3- 10 Technical data PM340, 3-ph. AC, Part 1
Line supply voltage 3-ph. 380 V to 480 V AC ±10%
PM340 6SL3210- 1SE11-3UA0 1SE11-7UA0 1SE12-2UA0 1SE13-1UA0 1SE14-1UA0
PM340 with integrated line
filter
- - - - - -
Frame size FSA FSA FSA FSA FSA
Output current
Rated current I
n
Base-load current I
H
for S6 operation (40%) l
s6
Peak current l
max
A
A
A
A
1.3
1.1
1.3
2.6
1.7
1.5
2.0
3.4
2.2
1.9
2.5
4.4
3.1
2.7
3.5
6.2
4.1
3.6
4.5
8.2
Unit rating
1)
on basis of I
n
on basis of I
H
kW
kW
0.37
0.37
0.55
0.55
0.75
0.75
1.1
1.1
1.5
1.5
Rated pulse frequency kHz 4 4 4 4 4
Power loss kW 0.10 0.10 0.10 0.11 0.11
Cooling air requirement m
3
/s 0.005 0.005 0.005 0.005 0.005
Sound pressure level L
pA
(1 m)
dB(A) < 45 < 45 < 45 < 45 < 45

Содержание

1008

Узнайте о технических характеристиках силовых модулей, включая параметры подключения, токи и защиту. Подробная информация для специалистов.

Кешбек Менеджер