High Performance Vector Control/Torque Control Inverter User Manual
78 Chapter 6 Parameter Description
analog feedback operation, the multi-section digital voltage reference is in priority to other reference
modes.
It can be used as process open loop frequency reference. Different multi-section frequency reference
can be selected in different terminal status by defining the multi-functional terminal X (multi-section
frequency terminals 1~4). ON means that the terminal is enabled, OFF means that the terminal is
disabled.
Note: Upon open loop operation, if the input terminal function sets the multi-section digital voltage and
multi-section frequency simultaneously, the multi-section frequency has the highest priority.
0.00~300.00 Hz(10.00Hz)
P4.25
P4.29 Multi-section frequency 8
0.00~300.00 Hz(28.00Hz)
P4.30 Multi-section frequency 9
0.00~300.00 Hz(30.00Hz)
P4.31 Multi-section frequency 10
0.00~300.00 Hz(35.00Hz)
P4.32 Multi-section frequency 11
0.00~300.00 Hz(38.00Hz)
P4.33 Multi-section frequency 12
0.00~300.00 Hz(40.00Hz)
P4.34 Multi-section frequency 13
0.00~300.00 Hz(45.00Hz)
P4.35 Multi-section frequency 14
0.00~300.00 Hz(48.00Hz)
P4.36 Multi-section frequency 15
0.00~300.00 Hz(50.00Hz)
Multi-section frequency 3 P4.24
0.00~300.00 Hz(8.00Hz)
Multi-section frequency 2 P4.23
0.00~300.00 Hz(5.00Hz)
Multi-section frequency 1 P4.22
0.00~300.00 Hz(25.00Hz) Multi-section frequency 7
P4.28
0.00~300.00 Hz(20.00Hz)
Multi-section frequency 6 P4.27
0.00~300.00 Hz(18.00Hz)
Multi-section frequency 5 P4.26
0.00~300.00 Hz(15.00Hz)
Multi-section frequency 4