High Performance Vector Control/Torque Control Inverter User Manual
110
Chapter 6 Parameter Description
Setting with operational panel / regulating frequency can be realized by the function. When the
operational panel is in the parameter display state of operation or stop,through operational panel / to
regulate frequency is the most direct and covenient way. Frequency value will save in the inverter and
superimposed on other frequency as final frequency.
Operational panel / digital regulating frequency control Pb.08 determines the function of operation
panel / adjustment volume.
Operational panel / integral rate Pb.09 determines the time it will take to refresh increment/decrement
for one time when adjusting with /.
Display of operational panel
Unit place
Action when power failure
0: mains loss save;
1: reset upon mains loss
Tens place
Action when stop
0: Maintain when stop;
1: Reset clear when deceleration or stop;
3: Reset during standby
Hundreds
place
Operational panel / regulation setting
0: Only valid when main reference is P0.05
open loop digital frequency setting
1: Valid during adjustment;
2: Invalid during adjustment
Thousands
place
0: With integral function;
1: Without integral function
Unit place: Action upon mains loss
0: After setting frequency by operational panel / adjustment, operational panel / adjustment
volume will be recorded automatically after power to the inverter is cut off.
1: After setting frequency by operational panel / adjustment, operational panel / adjustment
volume will be cleared automatically after power to the inverter is cut off.
Tens place: Action during shutdown
0: After shutdown, adjustment volume of / on operational panel keeps unchanged.
1: After shutdown, adjustment volume of / on operational panel will be cleared after carrying out stop
command.
2: After shutdown, adjustment volume of / on operational panel is cleared under the stop status.
Frequency cannot set by / under the stop status.
Hundreds place: Setting of / on operational panel
0: Only valid when the main reference is P0.05 open loop digital frequency setting (P0.04=0).
1: Valid under all frequency reference modes (P0.04 not specified).
2: Operational panel adjustment / disabled.
Thousands place: Setting of / on operational panel
0: With integral function. When the operation panel / adjustment is used to set the frequency, the
consistent adjustment in one direction has integral effect. The step length of adjustment starts from
0.01Hz, after every 10 times of adjustment, the step length will be increased by 10 times, and the