Tecorp HC2V9P43P7 [42/182] Attention for main circuit wiring

Tecorp HC2V9G4132 [42/182] Attention for main circuit wiring
High Performance Vector Control/TorqueControl Inverter User Manual
20 Chapter 3 Wiring of Incerter
Terminal symbol Terminal name and function description
R/L1, S/L2, T/L3 Three-phase AC input terminal
B1,
Ө
DC reactor connecting termina
B1, B2 Connecting terminal of braking resistor
U/T1, V/T2, W/T3 Three-phase AC output terminal
Grounding terminal PE
Note*The product equipped with braking unit as standard can realized common DC bus and braking
function, if needed connect DC reactor and braking function should contact factory, and the teminal of main
circuit B1B2、○
should change to
1、○
2/B1B2.
3.5.4 G-4090G/P-110G-4400/P-4450
The inverters of G-4090/P-4110G-4400/P-4450 adopt the top in bottom out wiring mode
Terminal symbol Terminal name and function description
R/L1, S/L2, T/L3 Three-phase AC input terminal
1,
2
DC reactor connecting terminal, if don’t connect DC reactor, the inverter
will not display after power on.
2,
Ө
DC power input terminal; DC output terminal of external braking unit
U/T1, V/T2, W/T3 Three-phase AC output terminal
Grounding terminal PE
3.6 Attention for Main Circuit Wiring
3.6.1 Power Supply Wiring
It is forbidden to connect the power cable to the inverter output terminal, otherwise, the internal
components of the inverter will be damaged.
To facilitate the input side overcurrent protection and power failure maintenance, the inverter shall
connect to the power supply through the circuit breaker or leakage circuit breaker and contactor.
Please confirm that the power supply phases, rated voltage are consistent with that of the nameplate,
otherwise, the inverter may be damaged.
3.6.2 Motor Wiring
It is forbidden to short circuit or ground the inverter output terminal, otherwise the internal components of
the inverter will be damaged.
Avoid short circuit the output cable and the inverter enclosure, otherwise there exists the danger of
electric shock.
It is forbidden to connect the output terminal of the inverter to the capacitor or LC/RC noise filter with
phase lead, otherwise, the internal components of the inverter may be damaged.

Содержание