SENSORSENSOR
SENSORSENSOR
SENSOR
CONNECTION DIAGRAMSCONNECTION DIAGRAMS
CONNECTION DIAGRAMSCONNECTION DIAGRAMS
CONNECTION DIAGRAMS
Direct current power supply 12÷28Vdc.
The sensor may be connected:
To the Hydrovar
®
directly on the terminal board X3. The sensor opens the NPN contact (black wire) 10
seconds (factory setting) after the water lack signal.
To a monitoring system (PLC), directly on the terminal board. A load resistance (pull-up) with a minimum
value of 1kOhm must be fitted on the outside.
To a system with a relay and direct current power supply. A recirculating (free-wheeling) diode must be
fitted on the outside.
General use, power supply 21÷27Vac.
The sensor may be connected to a system with a relay and alternating current power supply.
FF
FF
F
or protection sensor code kit, please see the accessories section.or protection sensor code kit, please see the accessories section.
or protection sensor code kit, please see the accessories section.or protection sensor code kit, please see the accessories section.
or protection sensor code kit, please see the accessories section.
Schemi di collegamento
Installazione meccanica
Schemi di collegamento
24
12
11
3
2
1
12, GND - Blue
11, Water lack signal input - Black
24, Power supply 12
÷28Vdc - Brown
Not used - white
X3 Hydrovar terminal board
DRP_006-en_a_sc
Power supply 12
÷
28Vdc - Brown
Not used - White
PLC
DRP_007-en_a_sc
Water lack signal - Black
GND - Blue
R min =1kOhm
Power supply 12
÷
28Vdc - Brown
Not used - White
Water lack signal - Black
GND - Blue
Imax= 50mA
DRP_008-en_a_sc
Power supply 21
÷
27Vac - Brown
Not used - White
DRP_009-en_a_sc
Water lack signal - Black
GND - Blue
Imax= 50mA