Daikin EWAQ170F-XR [25/67] Electrical specifications

Daikin EWAQ410F-SL [25/67] Electrical specifications
ELECTRICAL SPECIFICATIONS
EWAQ F-XR
190 210 240 300 330 340 310 170 MODEL
POWER SUPPLY
Phases Nr 3 3 3 3 3 3 3 3
Frequency
Hz
50
50
50
50
50
50
Voltage V 400 400 400 400 400 400 400 400
Voltage tolerance Minimum % -10% -10% -10% -10% -10% -10% -10% -10%
Voltage tolerance Maximum
%
+10%
+10%
+10%
+10%
+10%
+10%
UNIT
Maximum starting current A 276 332 346 401 472 501 472 501
Nominal running current cooling
A
107
116
125
139
180
180
Mximum running current
A
132
143
157
173
220
220
Maximum current for wires sizing A 145 158 173 190 242 274 242 274
FANS
Nominal running current cooling
A
10
10
13
13
16
16
COMPRESSORS
Phases Nr 3 3 3 3 3 3 3 3
Voltage V 400 400 400 400 400 400 400 400
Voltage tolerance Minimum
%
-10%
-10%
-10%
-10%
-10%
-10%
Voltage tolerance Maximum % +10% +10% +10% +10% +10% +10% +10% +10%
Maximum running current
A
61
61
66
66
72
72
80
80
102
102
117
102
102
117
Starting method --- DOL DOL DOL DOL DOL DOL DOL DOL
EWAQ F-XR
410
430
500
580
390
MODEL
POWER SUPPLY
Phases
Nr
3
3
3
3
3
Frequency
Hz
50
50
50
50
50
Voltage V 400 400 400 400 400 400
Voltage tolerance Minimum
%
-10%
-10%
-10%
-10%
-10%
Voltage tolerance Maximum % +10% +10% +10% +10% +10% +10%
UNIT
Maximum starting current A 618 632 646 628 754 801
Nominal running current cooling
A
226
239
255
300
347
Mximum running current A 283 296 310 377 419 465
Maximum current for wires sizing
A
311
326
341
415
460
FANS
Nominal running current cooling
A
21
21
21
26
26
COMPRESSORS
Phases Nr 3 3 3 3 3 3
Voltage
V
400
400
400
400
400
Voltage tolerance Minimum % -10% -10% -10% -10% -10% -10%
Voltage tolerance Maximum % +10% +10% +10% +10% +10% +10%
Maximum running current A
131
131
131
145
145
145
175
175
189
203
217
Starting method --- DOL DOL DOL DOL DOL DOL
Fluid: Water
Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%.
Maximum starting current: starting current of biggest compressor + current of the other compressors at maximum load + fans current at maximum load
Nominal current in cooling mode is referred to the following conditions: evaporator 12/7°C; ambient 35°C; compressors + fans current.
Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current
Maximum unit current for wires sizing is based on minimum allowed voltage
Maximum current for wires sizing: (compressors full load ampere + fans current) x 1,1.
Pagina 25 di 67