OPERATING LIMITS
Legend:
A = Fouling factors (m2 °C / kW)
B = Cooling capacity correction factor
C = Power input correction factor
D = EER correction factor
Table 3 - Air heat exchanger - Altitude correction factors
Legend:
A = Elevation above sea level (m)
B = Barometric pressure (mbar)
C = Cooling capacity correction factor
D = Power input correction factor
- Maximum operating altitude is 2000 m above sea level
- Contact factory in case the unit has to be installed at altitudes between 1000 and 2000 m above sea level
Table 4 - Minimum glycol percentage for low air ambient temperature
Legend:
AAT = Air Ambient Temperature (°C) (2)
A = Ethylene glycol (%) (1)
B = Propylene glycol (%) (1)
(1) Minimum glycol percentage to prevent freezing of water circuit at indicated air ambient temperature
(2) Air ambient temperature do exceed the operating limits of the unit, as protection of water circuit may be needed in winte
r season at
non-working conditions.
Table 5.1 - Available fan static pressure correction factors
The above data are referred to:
- Fan 800 mm diameter
- Fan speed 890 rpm or 900 rpm
Legend:
A = External Static Pressure (Pa)
B = Cooling Capacity (kW) Correction factor
C = Compressor Power Input (kW) Correction factor
D = Reduction of Maximum Condenser Inlet Air Temperature (°C)
Table 5.2 - Available fan static pressure correction factors