INSTALLATION NOTES
Warning Installation and maintenance of the unit must to be performed only by qualified personnel who have knowledge with local
codes and regulations, and experience with this type of equipment. Must be avoided the unit installation in places that could
be
considered dangerous for all the maintenance operations.
Handling
Care should be taken to avoid rough handling or shock due to dropping the unit. Do not push or pull the unit from
anything other than the base frame. Never allow the unit to fall during unloading o
r moving as this may result in serious damage. To
lift the unit, rings are provided in the base frame of the unit. Spreader bar and cables should be arranged to prevent damage
to the
condenser coil or unit cabinet.
Location
The units are produced for outside installation on roofs, floors or below ground level on condition that the area is free from
obstacles for the passage of the condenser air. The unit should be positioned on solid foundations and perfectly level; in th
e case of
installation on roofs
or floors, it may be advisable to arrange the use of suitable weight distribution beams. When the units are installed
on the ground, a concrete base at least 250 mm wider and longer than the unit’s footprint should be laid. Furthermore, this b
ase should
withstand the unit weight mentioned in the technical data table.
Space requirements The units are air-cooled, then it is important to respect the minimum distances which guarantee the best
ventilation of the condenser coils. Limitations of space reducing the air flow could cause significant reductions in cooling capacity and an
increase in electricity consumption.
To determinate unit placement, careful consideration must be given to assure a sufficient air flow across the condenser heat
transfer
surface. Two conditions must be avoided to achieve the best performance: warm air recirculation and coil starvation.
Both these conditions cause an increase of condensing pressures that results in reductions in unit efficiency and capacity.
Moreover the unique micropr
ocessor has the ability to calculate the operating environment of the air cooled chiller and the capacity to
optimize its performance staying on-line during abnormal conditions.
Each side of the unit must be accessible after installation for periodic servi
ce. 'Fig.1 and Fig.2' shows you minimum recommended
clearance requirements.
Vertical condenser air discharge must be unobstructed because the unit would have its capacity and efficiency significantly reduced.
If the units are positioned in places surrounde
d by walls or obstacles of the same height as the units, the units should follow the
minimum recommended clearance requirements shown in 'Fig.3 and Fig.4'. In the event the obstacles are higher than the units,
the
minimum recommended clearance requirements
are shown in 'Fig.5 and Fig.6'. Units installed closer than the minimum recommended
distance to a wall or other vertical riser may experience a combination of coil starvation and warm air recirculation, thus c
ausing
reduction in unit capacity and efficien
cy reductions. The microprocessor control is proactive in response “of design condition”. In the
case of single or compounded influences restricting airflow to the unit, the microprocessor will act to keep the compressor(s
) running
(at reduced capacity) rather than allowing a shut-off on high discharge pressure.
When two or more units are positioned side by side it is recommended that the condenser coils are at a minimum distance from
one
another as shown in 'Fig.7 and Fig.8'; strong wind could be the cause of air warm recirculation.
For other installation solutions, consult our technicians.
The above recommended information are representative of general installation. A specific evaluation should be done by contrac
tor
depending on the case.
Pagina 61 di 67
Содержание
- Air cooled scroll chillers 1
- Databook 1
- Ewaq f 1
- Performance according to en14511 1
- Certifications 2
- Code requirements safety and observant of laws directives 2
- Features and benefits 2
- Low operating cost and extended operating life 2
- Low operating sound levels 2
- Outstanding reliability 2
- Pagina 2 di 67 2
- Sound configurations 2
- Superior control logic 2
- Versions 2
- Cabinet and structure 3
- Compressor 3
- Condenser 3
- Condenser fans ø 800 3
- Electrical control panel 3
- Electronic expansion valve 3
- Evaporator plate heat exchanger 3
- General characteristics 3
- Pagina 3 di 67 3
- Refrigerant 3
- Refrigerant circuit 3
- General characteristics 4
- Pagina 4 di 67 4
- Supervising systems on request 4
- Options 5
- Options on request 5
- Pagina 5 di 67 5
- Standard options supplied on basic unit 5
- Options 6
- Pagina 6 di 67 6
- Capacity class in kw cooling 7
- Efficiency level 7
- Inverter 7
- Machine type 7
- Model series 7
- Nomenclature 7
- Pagina 7 di 67 7
- Refrigerant 7
- Sound level 7
- Ewaq f ss 8
- Pagina 8 di 67 8
- Technical specifications 8
- Ewaq f ss 9
- Pagina 9 di 67 9
- Technical specifications 9
- Ewaq f sl 10
- Pagina 10 di 67 10
- Technical specifications 10
- Ewaq f sl 11
- Pagina 11 di 67 11
- Technical specifications 11
- Ewaq f sr 12
- Pagina 12 di 67 12
- Technical specifications 12
- Ewaq f sr 13
- Pagina 13 di 67 13
- Technical specifications 13
- Ewaq f xs 14
- Pagina 14 di 67 14
- Technical specifications 14
- Ewaq f xs 15
- Pagina 15 di 67 15
- Technical specifications 15
- Ewaq f xl 16
- Pagina 16 di 67 16
- Technical specifications 16
- Ewaq f xl 17
- Pagina 17 di 67 17
- Technical specifications 17
- Ewaq f xr 18
- Pagina 18 di 67 18
- Technical specifications 18
- Ewaq f xr 19
- Pagina 19 di 67 19
- Technical specifications 19
- Electrical specifications 20
- Ewaq f ss 20
- Pagina 20 di 67 20
- Electrical specifications 21
- Ewaq f sl 21
- Pagina 21 di 67 21
- Electrical specifications 22
- Ewaq f sr 22
- Pagina 22 di 67 22
- Electrical specifications 23
- Ewaq f xs 23
- Pagina 23 di 67 23
- Electrical specifications 24
- Ewaq f xl 24
- Pagina 24 di 67 24
- Electrical specifications 25
- Ewaq f xr 25
- Pagina 25 di 67 25
- Ewaq f sl 26
- Ewaq f sr 26
- Ewaq f ss 26
- Pagina 26 di 67 26
- Sound levels 26
- Ewaq f xl 27
- Ewaq f xr 27
- Ewaq f xs 27
- Pagina 27 di 67 27
- Sound levels 27
- Operating limits 28
- Pagina 28 di 67 28
- Table 1 water heat exchanger minimum and maximum water δt 28
- Table 2 water heat exchanger fouling factors 28
- Operating limits 29
- Pagina 29 di 67 29
- Table 3 air heat exchanger altitude correction factors 29
- Table 4 minimum glycol percentage for low air ambient temperature 29
- Table 5 available fan static pressure correction factors 29
- Operating limits 30
- Pagina 30 di 67 30
- Water charge flow and quality 30
- Water content in cooling circuits 30
- Cooling performance 32
- Ewaq f ss 32
- Pagina 32 di 67 32
- Cooling performance 33
- Ewaq f ss 33
- Pagina 33 di 67 33
- Cooling performance 34
- Ewaq f ss 34
- Pagina 34 di 67 34
- Cooling performance 35
- Ewaq f sl 35
- Pagina 35 di 67 35
- Cooling performance 36
- Ewaq f sl 36
- Pagina 36 di 67 36
- Cooling performance 37
- Ewaq f sl 37
- Pagina 37 di 67 37
- Cooling performance 38
- Ewaq f sr 38
- Pagina 38 di 67 38
- Cooling performance 39
- Ewaq f sr 39
- Pagina 39 di 67 39
- Cooling performance 40
- Ewaq f sr 40
- Pagina 40 di 67 40
- Cooling performance 41
- Ewaq f xs 41
- Pagina 41 di 67 41
- Cooling performance 42
- Ewaq f xs 42
- Pagina 42 di 67 42
- Cooling performance 43
- Ewaq f xs 43
- Pagina 43 di 67 43
- Cooling performance 44
- Ewaq f xs 44
- Pagina 44 di 67 44
- Cooling performance 45
- Ewaq f xl 45
- Pagina 45 di 67 45
- Cooling performance 46
- Ewaq f xl 46
- Pagina 46 di 67 46
- Cooling performance 47
- Ewaq f xl 47
- Pagina 47 di 67 47
- Cooling performance 48
- Ewaq f xl 48
- Pagina 48 di 67 48
- Cooling performance 49
- Ewaq f xr 49
- Pagina 49 di 67 49
- Cooling performance 50
- Ewaq f xr 50
- Pagina 50 di 67 50
- Cooling performance 51
- Ewaq f xr 51
- Pagina 51 di 67 51
- Cooling performance 52
- Ewaq f xr 52
- Pagina 52 di 67 52
- Options technical data 53
- Pagina 53 di 67 53
- Single pump 2 poles 53
- Water pump kit 53
- Options technical data 54
- Pagina 54 di 67 54
- Twin pump 2 poles 54
- Water pump kit combination matrix 54
- Options technical data 55
- Options technical data 56
- Pagina 56 di 67 56
- Water pump kit technical information 56
- 2 3 4 5 6 7 8 57
- A m l i h g b c f e d 57
- Compressor evaporator condenser coil electrical panel fan evaporator water inlet evaporator water outlet slot for power and control panel connection 57
- Dimensional drawing 57
- Legend 57
- Pagina 57 di 67 57
- 2 3 4 5 6 7 8 58
- A m l i h g b c f e d 58
- Compressor evaporator condenser coil electrical panel fan evaporator water inlet evaporator water outlet slot for power and control panel connection 58
- Dimensional drawing 58
- Legend 58
- Pagina 58 di 67 58
- 2 3 4 5 6 7 8 59
- A m l i h g b c f e d 59
- Compressor evaporator condenser coil electrical panel fan evaporator water inlet evaporator water outlet slot for power and control panel connection 59
- Dimensional drawing 59
- Legend 59
- Pagina 59 di 67 59
- 2 3 4 5 6 7 8 60
- A m l i h g b c f e d 60
- Compressor evaporator condenser coil electrical panel fan evaporator water inlet evaporator water outlet slot for power and control panel connection 60
- Dimensional drawing 60
- Legend 60
- Pagina 60 di 67 60
- Handling 61
- Installation notes 61
- Location 61
- Pagina 61 di 67 61
- Space requirements 61
- Warning 61
- Installation notes 62
- Installation notes 63
- Pagina 63 di 67 63
- Condenser coil 64
- Dimensions 64
- Evaporator phe 64
- General 64
- Pagina 64 di 67 64
- Performance 64
- Refrigerant 64
- Sound level and vibrations 64
- Technical specifications 64
- Unit description 64
- Condensation control 65
- Condenser fans 65
- Controller 65
- Electrical control panel 65
- Hydronic kit options on request 65
- Low sound unit configurations on request 65
- Pagina 65 di 67 65
- Refrigerant circuit 65
- Technical specifications 65
- Controller main features 66
- High level communications interface on request 66
- Pagina 66 di 67 66
- Technical specifications 66
Похожие устройства
- Daikin EWAQ170F-XR Инструкция по монтажу
- Daikin EWAQ190F-XR Инструкция по эксплуатации
- Daikin EWAQ190F-XR Инструкция по монтажу
- Daikin EWAQ190F-XR Технические данные
- Daikin EWAQ210F-XR Инструкция по монтажу
- Daikin EWAQ210F-XR Инструкция по эксплуатации
- Daikin EWAQ210F-XR Технические данные
- Daikin EWAQ240F-XR Инструкция по монтажу
- Daikin EWAQ240F-XR Инструкция по эксплуатации
- Daikin EWAQ240F-XR Технические данные
- Daikin EWAQ300F-XR Инструкция по монтажу
- Daikin EWAQ300F-XR Инструкция по эксплуатации
- Daikin EWAQ300F-XR Технические данные
- Daikin EWAQ310F-XR Инструкция по монтажу
- Daikin EWAQ310F-XR Инструкция по эксплуатации
- Daikin EWAQ310F-XR Технические данные
- Daikin EWAQ330F-XR Инструкция по монтажу
- Daikin EWAQ330F-XR Инструкция по эксплуатации
- Daikin EWAQ330F-XR Технические данные
- Daikin EWAQ340F-XR Инструкция по монтажу