D-EIMAC01108-16EU - 14/248
Figure 4 - Minimum clearance requirements
7. A filter or device that can remove particles from the
fluid. The use of a filter extends the life of the
evaporator and pump and helps to keep the water
system in a better condition.
8. Evaporator has an electrical resistance with a
thermostat that ensures protection against water
freezing at ambient temperatures as low as 25°C.
All the other water piping/devices outside the unit
must therefore be protected against freezing.
9. The heat recovery device must be emptied of water
during the winter season, unless an ethylene glycol
mixture in appropriate percentage is added to the
water circuit.
Fig. 4C
Fig. 4B
Fig. 4A
Fig. 4F
Fig. 4E
Fig. 4G
Fig. 4H
Fig. 4D