Daikin UATYP240AMY1 [125/192] Dados eléctricos

Daikin UATYP240AMY1 [125/192] Dados eléctricos
7
Português
BOMBA DE CALOR (R22)
DADOS ELÉCTRICOS
MODELO
UAT180 UAT240 UAT280 UAT320 UAT450
FORNECIMENTO DE ENERGIA
V/ph/Hz 400 / 3N ~ / 50
ALCANCE DA VOLTAGEM
V 380 ~ 415
COURANT CONTINU MAXI (COMP)
A 14,0 23,0 26,9 27,5 23,0 x 2
INTENSITÉ DE PLEINE CHARGE (FLA, COMP)
A 12,1 15,6 16,9 22,3 15,6 x 2
INTENSITÉ À ROTOR BLOQUÉ (LRA, COMP)
A 74 95 118 118 95 x 2
MODELO
UAT560 UAT700 UAT850 UATC10 UATC12
FORNECIMENTO DE ENERGIA
V/ph/Hz 400 / 3N ~ / 50
ALCANCE DA VOLTAGEM
V 380 ~ 415
COURANT CONTINU MAXI (COMP)
A 26,9 x 2 27,5 x 2 42,0 x 2 35,0, 50,0 50,0 x 2
INTENSITÉ DE PLEINE CHARGE (FLA, COMP)
A 16,9 x 2 22,3 x 2 30,0 x 2 24,0, 30,0 30,0 x 2
INTENSITÉ À ROTOR BLOQUÉ (LRA, COMP)
A 118 x 2 118 x 2 174 x 2 175, 215 215 x 2
APENAS ARREFECIMENTO (R22)
MODELO
UATY180 UATY240 UATY280 UATY320 UATY450
FORNECIMENTO DE ENERGIA
V/ph/Hz 400 / 3N ~ / 50
ALCANCE DA VOLTAGEM
V 380 ~ 415
COURANT CONTINU MAXI (COMP)
A 17,0 22,0 31,0 27,5 22,0 x 2
INTENSITÉ DE PLEINE CHARGE (FLA, COMP)
A 15,0 19,5 23,0 22,3 19,5 x 2
INTENSITÉ À ROTOR BLOQUÉ (LRA, COMP)
A 101 84 81 118 84 x 2
MODELO
UATY560 UATY700 UATY850 UATYC10 UATYC12
FORNECIMENTO DE ENERGIA
V/ph/Hz 400 / 3N ~ / 50
ALCANCE DA VOLTAGEM
V 380 ~ 415
COURANT CONTINU MAXI (COMP)
A 31,0 x 2 27,5 x 2 42,0 x 2 35,0, 50,0 50,0 x 2
INTENSITÉ DE PLEINE CHARGE (FLA, COMP)
A 23,0 x 2 22,3 x 2 30,0 x 2 24,0, 30,0 30,0 x 2
INTENSITÉ À ROTOR BLOQUÉ (LRA, COMP)
A 81 x 2 118 x 2 174 x 2 175, 215 215 x 2
BOMBA DE CALOR (R407C)
MODELO
UATYP180 UATYP240 UATYP280 UATYP320 UATYP450
FORNECIMENTO DE ENERGIA
V/ph/Hz 400 / 3N ~ / 50
ALCANCE DA VOLTAGEM
V 380 ~ 415
COURANT CONTINU MAXI (COMP)
A 17,0 23,0 26,9 31,0 23,0 x 2
INTENSITÉ DE PLEINE CHARGE (FLA, COMP)
A 15,0 15,9 16,9 22,3 15,9 x 2
INTENSITÉ À ROTOR BLOQUÉ (LRA, COMP)
A 101 95 118 118 95 x 2
MODELO
UATYP560 UATYP700 UATYP850 UATYPC10 UATYPC12
FORNECIMENTO DE ENERGIA
V/ph/Hz 400 / 3N ~ / 50
ALCANCE DA VOLTAGEM
V 380 ~ 415
COURANT CONTINU MAXI (COMP)
A 26,9 x 2 31,0 x 2 42,0 x 2 35,0, 50,0 50,0 x 2
INTENSITÉ DE PLEINE CHARGE (FLA, COMP)
A 16,9 x 2 22,3 x 2 32,0 x 2 24, 30 30,0 x 2
INTENSITÉ À ROTOR BLOQUÉ (LRA, COMP)
A 118 x 2 118 x 2 174 x 2 175, 215 215 x 2
MODELO
UATP180 UATP240 UATP280 UATP320 UATP450
FORNECIMENTO DE ENERGIA
V/ph/Hz 400 / 3N ~ / 50
ALCANCE DA VOLTAGEM
V 380 ~ 415
COURANT CONTINU MAXI (COMP)
A 14,0 23,0 26,9 31,0 23,0 x 2
INTENSITÉ DE PLEINE CHARGE (FLA, COMP)
A 13,0 15,9 16,9 22,3 15,6 x 2
INTENSITÉ À ROTOR BLOQUÉ (LRA, COMP)
A 74 95 118 118 95 x 2
MODELO
UATP560 UATP700 UATP850 UATPC10 UATPC12
FORNECIMENTO DE ENERGIA
V/ph/Hz 400 / 3N ~ / 50
ALCANCE DA VOLTAGEM
V 380 ~ 415
COURANT CONTINU MAXI (COMP)
A 26,9 x 2 31,0 x 2 42,0 x 2 35,0, 50,0 50,0 x 2
INTENSITÉ DE PLEINE CHARGE (FLA, COMP)
A 16,9 x 2 22,3 x 2 30,0 x 2 24, 30 30,0 x 2
INTENSITÉ À ROTOR BLOQUÉ (LRA, COMP)
A 118 x 2 118 x 2 174 x 2 175, 215 215 x 2
APENAS ARREFECIMENTO (R407C)
8 IM-RTA-0107(2)DKdenv_PT.indd 78 IM-RTA-0107(2)DKdenv_PT.indd 7 3/20/12 11:45:39 AM3/20/12 11:45:39 AM

Содержание