Daikin UATYP240AMY1 [16/192] Warning

Daikin UATYPC12AMY18 [16/192] Warning
10
-15
-10
-5
0
10
15 20 25 30
5
10
15
27
20
Wiring Example and Selection of Circuit Breaker 380 ~ 415V, 3N ~ /50
Note:
A main switch or other means for disconnection, having a contact separation in all poles, must be incorporated in xed wiring in
accordance with local and national legislation.
The unit is to be wired directly from an electrical distribution board either by a circuit breaker (preferred) or HRC fuse.
Fix the power supply wiring to control module. Connect control wiring to control terminal block through the control box’s hole.
Earth wiring must be connected.
The power supply cord must be equivalent to H07RN-F which is the minimum requirement, and to be used in protective tube.
WIRE CONNECTION
MODEL
POWER CABLE
(mm
2
)
BREAKER
CAPACITY (A)
OVER CURRENT
PROTECTION SWITCH (A)
EARTH CABLE
(mm
2
over)
UAT(Y)(P)180 8.4 32 32 8.4
UAT(Y)(P)240 8.4 32 32 8.4
UAT(Y)(P)280 13.3 50 50 13.3
UAT(Y)(P)320 13.3 50 50 13.3
UAT(Y)(P)450 13.3 50 50 13.3
UAT(Y)(P)500 21.2 63 63 21.2
UAT(Y)(P)700 33.6 80 80 33.6
UAT(Y)(P)850 42.4 100 100 42.4
UAT(Y)(P)C10 60.0 125 125 60.0
UAT(Y)(P)C12 60.0 125 125 60.0
Ensure the operating temperature is in allowable range.
-10
-5
0
10
20
30
40
50
10 15 20 25 30
54
24
Cooling (R22)
Cooling Only Unit & Cooling Mode For Heat Pump Unit
Cooling (R407C)
Cooling Only Unit & Cooling Mode For Heat Pump Unit
Outdoor temp. (°C DB)
Outdoor temp. (°C DB)
Indoor temp. (°C DB)
OPERATING RANGE
The use of your air conditioner
outside the range of working
temperature and humidity can
result in serious failure.
! CAUTION:
Note:
WB = Wet Bulb
DB = Dry Bulb
! WARNING
Before working on this unit, isolate from the power supply.
Electrical wiring to this unit and the remote controller shall be installed in accordance with the appropriate
requirements of the local wiring code.
-10
-5
0
10
20
30
40
50
10 15 20 25 30
46
24
Heating (R22 & R407C)
Heat Pump Unit Only
Outdoor temp. (°C WB)
Indoor temp. (°C WB) Indoor temp. (°C WB)
1 IM-RTA-0107(2)DKdenv_EN.indd 101 IM-RTA-0107(2)DKdenv_EN.indd 10 3/15/12 9:11:32 AM3/15/12 9:11:32 AM