Si38-606 Troubleshooting by Indication on the Remote Controller
Troubleshooting 135
2.15
E4
Outdoor Unit: Actuation of Low Pressure Sensor
Remote
Controller
Display
E4
Applicable
Models
RXM8, 10M
Method of
Malfunction
Detection
Malfunction
Decision
Conditions
Error is generated when the low pressure is dropped under specific pressure.
Supposed
Causes
Abnormal drop of low pressure (Refer to page 54 for Low Pressure Control)
Defect of low pressure sensor
Defect of outdoor unit PC board
Stop valve is not opened.
Troubleshooting
1: Voltage measurement point
2: Refer to pressure sensor, pressure / voltage characteristics table on P234.
(V2791)
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Is the malfunction
due to abnormal drop of low
pressure?
Measure
the voltage (VL)
of X45A pin No. (2) - (3)
of outdoor PC board (A1P).1
Is the relationship
between low
voltage and VL
normal?
Out of gas, refrigerant system
clogging, wiring and piping wrong
connection, stop valve closed,
electronic expantion valve fully
close malfunction.
Replace the low pressure sensor.
Replace outdoor unit PC board
(A1P).
NO
NO
YES
YES
Is stop valve opened?
Open stop valve.
NO
YES