Basic Control Si38-606
46 Function
2.2 Compressor PI Control
Compressor PI Control
Carries out the compressor capacity PI control to maintain Te at constant during cooling
operation and Tc at constant during heating operation to ensure stable unit performance.
[Cooling operation]
Compressor Step Control
RXM8, 10M
Notes:
1. INV : Inverter compressor
STD1 : Standard compressor 1
2. Depending on the operating conditions of compressors, the compressors may run in patterns other than those
aforementioned.
Controls compressor capacity to adjust Te to
achieve target value (TeS).
Te : Low pressure equivalent saturation temperature
(°C)
Te setting TeS : Target Te value
(Varies depending on Te setting, operating
frequency, etc.)
LM (Normal)
(factory
setting)
H
369
STEP INV STD1
1 52Hz OFF
2 57Hz OFF
3 62Hz OFF
4 68Hz OFF
5 74Hz OFF
6 81Hz OFF
7 88Hz OFF
8 96Hz OFF
9 104Hz OFF
10 110Hz OFF
11 116Hz OFF
12 124Hz OFF
13 133Hz OFF
14 143Hz OFF
15 158Hz OFF
16 165Hz OFF
17 177Hz OFF
18 189Hz OFF
19 202Hz OFF
20 210Hz OFF
21 52Hz ON
22 74Hz ON
23 96Hz ON
24 116Hz ON
25 133Hz ON
26 158Hz ON
27 177Hz ON
28 202Hz ON
29 210Hz ON